Packaged Cooling with
Electric Heat Rooftop Units
Precedent™
TSC060-120
50 Hz
RT-PRC016-EN
February 2004
Contents
Introduction
2
4
Features and Benefits
Application Considerations
Selection Procedure
Model Number Description
General Data
9
10
12
13
14
33
34
35
36
44
45
Performance Data
Zone Controls
Electrical Data
Jobsite Connections
Dimensional Data
Weights
Mechanical Specifications
RT-PRC016-EN
3
Features and
Benefits
Easy Access Panels
Remove two screws for access to the
standardized internal components and
wiring.
Easy-Adjust Idler Arm
With the Easy-Adjust Idler Arm, the belt
and sheaves can be quickly adjusted
without moving the mounted fan motor.
The result is a major savings in time and
money.
Patented Condenser Coil
Precedent boasts a patented 1+1+1
Hybrid coil, permanently gapped for
easy of cleaning.
Unit Cabinet
The compact cabinet with rounded
corners takes up less room and is less
costly to ship. The beveled and ribbed
top is not only aesthetically pleasing, it is
designed to prevent water from pooling.
Single Point Power
A single electrical connection powers the
unit.
Colored And Numbered Wiring
You save time and money tracing wires
and diagnosing the unit.
Convertible Units
• The units ship in a downflow
configuration. They can be easily
converted to horizontal by simply
moving two panels.
Sloped Drain Pans
Every Precedent unit has a non-
corrosive, removable, double-sloped
drain pan that’s easy to clean and
reversible to allow installation of drain
trap on either side of the unit.
• Units come complete with horizontal
duct flanges so the contractor doesn’t
have to field fabricate them. These
duct flanges are a time and cost saver.
Compressors
Through the Base Condensate
Every unit includes provisions for
through the base condensate drain
connections. This allows the drain to be
connected through the roof curb instead
of a roof penetration.
Precedent™ contains the best
compressor technology available to
achieve the highest possible
performance. Our compressor line
includesTrane built reciprocating and
scrolls.
Foil-Faced Insulation
Easy Access Panels
All panels in the Evaporator section of
the unit have cleanable foil-faced
insulation. All edges are either captured
or sealed to ensure no fibers get into the
airstream.
Easy access panels reduce the number of
possible water entry points.
Low Ambient Cooling
All Precedent units have cooling
capabilities down to 0°F as standard.
Unit Base
For added water integrity, Precedent has
a raised 29 mm (11/8") lip around the
unit’s downflow supply and return to
prevent water from blowing into the
ductwork.
RT-PRC016-EN
4
Features and
Benefits
Flexible Applications
Standardized Components
• Only two roof curbs for the 5-10 ton
Precedent line. . .simplifies curb
• RseelleiacTtieolnm. icroprocessor controls to
meet either the simple or the more
complex application.
• Components are placed in the same
location on all Precedent™ units.
Familiarize yourself with one Precedent
and you are familiar with every
Precedent.
• Airflow is outstanding. The Precedent
can replace an older machine with old
ductwork and, in many cases, improve
comfort through better air distribution.
• Belt drive — standard or oversized
supply fan motors meet a wide airflow
range.
• Precedent offers ultimate flexibility.
Options and components are not pre-
packaged at the factory. Units are built
to order in our standard “shortest in
the industry” ship cycle time.
Easy Access Low Voltage Terminal
Board
Precedent’s Low Voltage Terminal Board
is external to the electrical control
cabinet. It is extremely easy to locate and
attach the thermostat wire. This is
another cost and time saving installation
feature.
Low Voltage Connections
The wiring of the low voltage
connections to the unit and the zone
sensors is as simple as 1-1, 2-2, and 3-3.
This simplified system makes it easy for
the installer to wire
Single-Side Service
Single-side service is standard on all
Precedent units.
RT-PRC016-EN
5
Features and
Benefits
• Eliminates the need for field-installed
components with its built-in anti-
short-cycle timer, time delay relay
and minimum ‘’on’’ time controls.
These controls are factory tested to
assure proper operation.
• Requires no special tools to run the
Precedent unit through its paces
during testing. Simply place a
jumper betweenTest 1 andTest 2
terminals on the Low Voltage
Terminal Board and the unit will walk
through its operational steps. The
unit automatically returns control to
the zone sensor after stepping
through the test mode a single time,
even if the jumper is left on the unit.
Micro Controls
Several years ago,Trane was the first to
introduce microprocessor controls into
the Light Commercial Market. That
design, along with immeasurable
experience, has provided the
technology for Trane’s second-
generation ReliaTel™ microprocessor
controls.
• As long as the unit has power and
the LED is lit, the Micro is
operational. The light indicates that
the Micro is functioning properly.
• Features expanded diagnostic
capabilities when used with Trane’s
Integrated Comfort ™ Systems.
• As an energy benefit, softens
electrical ‘’spikes’’ by staging on fans,
compressors and heaters.
ReliaTel™ Micro:
• Provides unit control for heating,
cooling, and ventilating by utilizing
input from sensors that measure
outdoor and indoor temperature.
• The Intelligent Fallback or Adaptive
Control is a benefit to the building
occupant. If a component goes
astray, the unit will continue to
operate at predetermined
• Improves quality and reliability
through the use of time-tested
microprocessor controls and logic.
temperature set points.
• Intelligent Anticipation is a standard
feature of the Micro. Functioning
constantly, the Micro and zone
sensors work together in harmony,
to provide tight comfort control.
• Prevents the unit from short cycling,
considerably improving compressor
life.
• Ensures that the compressor will run
for a specific amount of time, which
allows oil to return for better
lubrication, enhancing the reliability of
the compressor.
• Reduces the number of components
required to operate the unit, thereby
reducing possibilities for component
failure.
RT-PRC016-EN
6
Features and
Benefits
Factory-installed Options
Hinged Access Doors
The following options round-out the
complete line of Precedent™ options:
These doors permit easy access to the
filter, fan/heat, and compressor/control
sections. They reduce the potential roof
damage from screws or sharp access
door corners.
— 0 - 50% Manual or Motorized
Outside Air
— Hail Protection Quality Coil Guards
— Electric Heaters (available as field
installed accessories)
Economizer
— Discharge Air Sensor
Equipped with either dry bulb, reference
or comparative enthalpy sensing, this
feature provides free cooling as the
outdoor temperature and/or humidity
decreases. Economizers, correctly
installed, offer a valuable energy
savings. Factory-installed economizers
save time and ensure proper installation.
— Wide array of Zone Sensors and
Thermostats
— Factory built Roof Curb
One of Our Finest Assets:
Trane Sales Representatives are a
Support group that can assist you with:
— Product
Phase Monitor
— Application
Phase monitor shall provide 100%
protection for motors and compressors
against problems caused by phase loss,
phase imbalance, and phase reversal.
Phase monitor is equipped with an LED
that provides an ON or FAULT indicator.
— Service
— Training
— Special Applications
— Specifications
— Computer Programs and much more
Precedent has the features and benefits
that make it first class in the light
commercial rooftop market. Designed
with input from field contractors and
engineers, its airflow performance is
outstanding.
Clogged Filter/Fan Fail Switches
These sensors allow a zone sensor
service light or Integrated Comfort
System to indicate a dirty filter or a fan
that’s not working. The field installation
charges for these valuable feedback
devices often eliminate them from
consideration. Factory installation can
make such features a good investment.
Precedent…The same Trane
quality…with added flexibility.
Comm-3/4Trane Communication
Interface
Available factory or field-installed. This
module when applied with ReliaTel™
easily interfaces with Trane’s Integrated
Comfort™ System.
RT-PRC016-EN
7
Features and
Benefits
Quality And Reliability Testing
• We perform a 100% coil leak test at the
factory. The evaporator and condenser
coils are leak tested at 1375 kPa (200
psig) and pressure tested to 3100 kPa
(450 psig).
• All Precedent™ designs were rigorously
rain tested at the factory to ensure
water integrity.
• Actual shipping tests were performed
to determine packaging requirements.
Units were test shipped around the
country to determine the best
packaging.
• All parts are inspected at the point of
final assembly. Sub-standard parts are
identified and rejected immediately.
• Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorousTrane
requirements.
• Factory shake and drop tests were
used as part of the package design
process to help assure that the unit
arrives at the job site in top condition.
We test designs at our factory not on
our customers!
• Rigging tests include lifting a unit into
the air and letting it drop one foot,
assuring that the lifting lugs and rails
hold up under stress.
VariTrac™
VariTrac
When Trane’s changeover VAV System
for light commercial applications is
coupled with Precedent, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.
RT-PRC016-EN
8
Application
Considerations
Application of this product should be
within the cataloged airflow and cooling
considerations.
Condensate Trap
The evaporator is a draw-thru
configuration. A trap must be field
provided prior to start-up on the cooling
cycle.
Low Ambient Cooling
The Precedent™ line features, with
ReliaTel™ microprocessor controls, low
ambient cooling down to 18°C (0°F).
Contact your localTrane Representative
for more assistance with low ambient
cooling applications.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate service
maximum capacity and peak operating
efficiency. Actual clearances which
appear inadequate should be reviewed
with the localTrane sales personnel.
Barometric Relief
This product line offers an optional
barometric relief damper. for use in
conjunction with economizer option.
This accessory consists of gravity
dampers which open with increased
pressure. As the building air pressure
increases, the pressure in the unit return
air section also increases, opening the
dampers and relieving the conditioned
space.
Unit Pitch
These units have reversible sloped
condensate drain pans. Units must be
installed level, any unit slope must be
toward the side of unit where
condensate drain is connected.
NOTE: THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER
DURING ECONOMIZING OPERATION
IS SYSTEM RELATED.
PRESSURE DROP OF THE RETURN AIR
SYSTEM SHOULD BE CONSIDERED TO
CONTROL BUILDING PRESSURIZA-
TION.
RT-PRC016-EN
9
Selection
Procedure - SI Units
Cooling Capacity
Step 3
Heating Capacity
In order to select the correct unit which
meets the building’s requirements, the
fan motor heat must be deducted from
the gross cooling capacity.The amount
of heat that the fan motor generates is
dependent on the effort by the motor -
cfm and static pressure.To determine
the total unit static pressure:
Step 1
Step 1
Calculate the building’s total and sensible
cooling loads at design conditions. Use
theTrane calculation methods or any
other standard accepted method.
Calculate the building heating load using
theTrane calculation form or other
standard accepted method.
Step 2
Factors used in unit selection:
Size the system heating capacity to
match the calculated building heating
load. The following are building heating
requirements:
A
Total Cooling Load: 16.7 kW
External Static (duct system)
110 Pa
B
A
Sensible Cooling Load: 11.7 kW
Standard Filter 1 in.
from Table PD-21
37 Pa
Total heating load of 5 kW
C
B
Airflow: 3400 m3/h
Economizer
5 Pa
2000 cfm
D
(100% Return Air)
Table PD-21
from
C
Electrical Characteristics: 380-415/50/3
380 volt/3 phase Power Supply
E
Electric Heater Size 7.5 kW
from Table PD-21
17 Pa
The electric heat accessory capacities are
listed inTable PD-23. From the table, the
smallest heater will deliver 7.5 kW at
380 V. Referring toTable ED-2, the
electric heater selection is
Summer Design Conditions: Entering
Evaporator Coil: 27 DB, 19 WB Outdoor
Ambient: 35
Total Static Pressure
169 Pa
Note: The Evaporator Fan Performance
Table PD-6 has deducted the pressure
drop for a 25 mm filter already in the
unit (see note belowTable PD-6).
Therefore, the actual total static pressure
is 169-17 (fromTable PD-21) = 152 Pa.
F
External Static Pressure: 110 Pa
BAYHTRR412A.
Air Delivery Selection
Step 2
External static pressure drop through the
air distribution system has been
calculated to be 110 Pa. FromTable PD-
21 static pressure drop through the
economizer is 5 Pa and the 7.5 kW heater
is 17 Pa (110 + 5 + 17). EnterTable PD-6
for a TSC060AD at 3400 m3/h and 132 Pa
static pressure. The standard motor will
give the desired airflow at a rated kW of
0.64.
Table PD-1 shows that aTSC060AD has a
gross cooling capacity of 17.8 kW and
14.4 kW sensible capacity at 3400 m3/h
and 35 DB outdoor ambient with 27 DB,
19 WB air entering the evaporator.
With 3400 m3/h and 152 Pa
Table PD-6 shows .67 kW for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
To Find Capacity at Intermediate
Conditions Not in the Table
Fan Motor Heat (kw) =
1.144 x (Fan kW) + 0.132
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
= 1.144 x 0.67 + 0.132 = 0.90 kW
Now subtract the fan motor heat from
the gross cooling capacity of the unit:
Net Total Cooling Capacity
Accessory Selection
Select accessories needed to
accommodate the application.
= 17.8 kW - 0.9 = 16.9 kW.
Net Sensible Cooling Capacity
= 14.4 kW - 0.9 = 13.5 kW.
Step 4
If the performance will not meet the
required load of the building’s total or
sensible cooling load, try a selection at
the next higher size unit.
RT-PRC016-EN
10
Selection
Procedure - IP Units
Step 3
Heating Capacity
Cooling Capacity
In order to select the correct unit which
meets the building’s requirements, the
fan motor heat must be deducted from
the gross cooling capacity.The amount
of heat that the fan motor generates is
dependent on the effort by the motor -
cfm and static pressure.To determine
the total unit static pressure:
Step 1
Step 1
Calculate the building heating load using
theTrane calculation form or other
standard accepted method.
Calculate the building’s total and sensible
cooling loads at design conditions. Use
theTrane calculation methods or any
other standard accepted method.
Step 2
Size the system heating capacity to
match the calculated building heating
load. The following are building heating
requirements:
Factors used in unit selection:
A
Total Cooling Load: 59 MBh
External Static (duct system)
0.45 wg
B
A
Sensible Cooling Load: 40 MBh
Standard Filter 1 in.
from Table PD-21a
0.15 wg
Total heating load of 15 MBH
C
B
Airflow: 2000 cfm
Economizer
0.02 wg
from
2000 cfm
D
(100% Return Air)
Table PD-21a
C
Electrical Characteristics: 380-415/50/3
380 volt/3 phase Power Supply
E
Electric Heater Size 26 MBh
from Table PD-21a
0.07 wg
The electric heat accessory capacities are
listed inTable PD-23a. From the table,
the smallest heater will deliver 26 MBh at
380 volts. Referring toTable ED-2, the
electric heater accessory selection is
BAYHTRR412A.
Summer Design Conditions: Entering
Evaporator Coil: 80 DB, 67 WB Outdoor
Ambient: 95
Total Static Pressure
0.69 wg
Note: The Evaporator Fan Performance
Table PD-6a has deducted the pressure
drop for a 1 in. filter already in the unit
(see note below Table PD-6a). Therefore,
the actual total static pressure is 0.69 -
0.15 (fromTable PD-21a) = 0.50 wg.
F
External Static Pressure: 0.45 in. wg
Step 2
Air Delivery Selection
Table PD-1a shows that aTSC060AD has
a gross cooling capacity of 62.0 MBh and
46.4 MBh sensible capacity at 2000 cfm
and 95 DB outdoor ambient with 80 DB,
67 WB air entering the evaporator.
External static pressure drop through the
air distribution system has been
calculated to be 0.45 inches of water.
FromTable PD-21a static pressure drop
through the economizer is 0.02 and the
26 kW heater is 0.07 inches of water (0.45
+ 0.02 + 0.07). EnterTable PD-6a for a
TSC060AD at 2000 cfm and 0.54 static
pressure. The standard motor will give
the desired airflow at a rated bhp of
about 1.01.
With 2000 cfm and 0.50 wg.
Table PD-6a shows .83 bhp for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
To Find Capacity at Intermediate
Conditions Not in the Table
Fan Motor Heat (MBh) =
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
2.915 x (Fan BHP) + 0.451
= 2.915 x 0.83 + 0.451 = 2.87 MBh
Now subtract the fan motor heat from
the gross cooling capacity of the unit:
Net Total Cooling Capacity
Accessory Selection
Select accessories needed to
accommodate the application.
= 62 MBh - 2.87 = 59.1 MBh.
Net Sensible Cooling Capacity
= 46.4 MBh - 2.87 = 43.5 MBh.
Step 5
If the performance will not meet the
required load of the building’s total or
sensible cooling load, try a selection at
the next higher size unit.
RT-PRC016-EN
11
Model
Number
Description
T
1
S
2
C 060 A
3 4,5,6 7
D
8
R
9
O
A
**
C
0
0
0
0
0
0
0
0
0
0
1
10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25
Digit 1 - Unit Function
Digits 12, 13 - Service Sequence
** Factory Assigned
Digit 18 - Through the Base Provisions
T = DX Cooling
=
0 = No Through the Base Provisions
Digit 2 - Efficiency
Digit 14 - Fresh Air Selection
Digit 19 - Disconnect/Circuit Breaker/Phase
Monitor (3 phase only)
S = Standard Efficiency
0 = No Fresh Air
A = Manual Outside Air Damper 0-50%
B = Motorized Outside Air Damper 0-50%
C = Economizer, Dry Bulb 0-100%
without Barometric Relief
0 = No Disconnect or Circuit Breaker
3 = Phase Monitor Only (No Disconnect,
No Circuit Breaker)
Digit 3 - Airflow
C = Convertible
D = Economizer, Dry Bulb 0-100%
with Barometric Relief
E = Economizer, Reference Enthalpy
0-100% without Barometric Relief
F = Economizer, Reference Enthalpy
0-100% with Barometric Relief
G = Economizer, Comparative Enthalpy
0-100% without Barometric Relief
H = Economizer, Comparative Enthalpy
0-100% with Barometric Relief
Digit 20 - Convenience Outlet
Digits 4,5,6 - Nominal Gross Cooling
Capacity (MBh)
0 = No Convenience Outlet
kW
060 = 17.6
072 = 21.1
090 = 26.4
102 = 29.9
120 = 35.1
Tons
5
Digit 21 - Communications Options
6
0 = No Communications Interface
1 = Comm-3/4 Communications Interface
2 = Comm-5 Communications Interface
7.5
8.5
10
Digit 22 - Refrigeration System Option
Digit 7 - Major Design Sequence
0 = Standard Refrigeration System
Digit 15 - Supply Fan/Drive Type/Motor
A = First
0 = Standard Drive
1 = Oversized Motor
Digit 23 - Refrigeration Controls
Digit 8 - Unit Voltage
0 = No Refrigeration Control
D = 380-415/50/3
Digit 16 - Hinged Service Access/Filters
Digit 24 - Smoke Detector
0 = Standard Panels/Standard Filters
A = Hinged Access Panels/Standard Filters
B = Standard Panels/
50 mm (2”) Pleated Filters
C = Hinged Access Panels/
50 mm (2”) Pleated Filters
Digit 9 - Unit Controls
R = ReliaTel™ Microprocessor
0 = No Smoke Detector
Digit 25 - Monitoring Controls
Digit 10 - Heating Capacity
0 = No Monitoring Control
1 = Clogged Filter Switch
2 = Fan Failure Switch
3 = Discharge Air Sensing Tube
4 = Clogged Filter Switch and Fan Fail
Switch
5 = Clogged Filter Switch and Discharge
Air Sensing Tube
6 = Fan Fail Switch and Discharge Air
Sensing Tube
0 = No Electric Heat
Digit 17 - Condenser Coil Protection
Digit 11 - Minor Design Sequence
0 = Standard Coil
A = First Sequence
1 = Standard Coil with Hail Guard
2 = Epoxy Coated Condenser Coil
3 = Epoxy Coated Condenser Coil with
Hail Guard
7 = Clogged Filter and Fan Fail Switches
and Discharge Air Sensing Tube
RT-PRC016-EN
12
General
Data
Table GD - 1 — General Data
Convertible Units
Convertible Units
Convertible Units
TSC090AD
Convertible Units
TSC102AD
Convertible Units
TSC120AD
TSC060AD
TSC072AD
Cooling Performance 1
Gross Capacity - kW (MBh)
COP (EER)2
18.2 (62.0)
2.99 (10.2)
3400 (2000)
3400 (2000)
17.3 (59.0)
5.78
23.2 (79.0)
3.08 (10.5)
4080 (2400)
3570 (2100)
22.0 (75.0)
7.14
26.7 (91.0)
3.02 (10.3)
5100 (3000)
4460 (2625)
25.2 (86.0)
8.35
31.1 (106.0)
3.02 (10.3)
5780 (3400)
5100 (3000)
29.9 (102.0)
9.90
34.9 (119.0)
2.99 (10.2)
6800 (4000)
5950 (3500)
33.1 (113.0)
11.08
Nominal Airflow - m3/h (cfm)
Rated Airflow - m3/h (cfm)
Net Capacity - kW (MBh)
System Power - kW
Compressor
Number -Type
Outdoor Sound Rating - dB 3
Outdoor Coil -Type
1-Climatuff Scroll
80
1-Trane 3-D Scroll
85
1-Trane 3-D Scroll
85
2-Climatuff Scroll
83
2-Climatuff Scroll
79
Lanced
Lanced
Lanced
Lanced
Lanced
Tube Size - in. OD
0.3125
1.02 (10.96)
3 / 17
0.3125
1.29 (13.88)
2 / 17
0.3125
1.29 (13.88)
2 / 17
0.3125
1.75 (18.89)
2 / 17
0.3125
2.41 (25.92)
2 / 17
Face Area - m2 (sq ft)
Rows / FPI
Indoor Coil -Type
Lanced
Lanced
Lanced
Lanced
Lanced
Tube Size OD - in.
0.3125
0.62 (6.68)
3 / 16
0.3125
0.92 (9.89)
2 / 16
0.3125
0.92 (9.89)
3 / 16
0.3125
1.15 (12.36)
3 / 16
0.3125
1.15 (12.36)
4 / 16
Face Area - m2 (sq ft)
Rows / FPI
Refrigerant Control
Drain Connection No. / Size - in.
Outdoor Fan -Type
No. Used / Diameter - in.
DriveType / No. Speeds
CFM
Short Orifice
1 / 0.75 NPT
Propeller
1 / 22
Direct / 1
2900
Short Orifice
1 / 0.75 NPT
Propeller
1 / 26
Direct / 1
5100
Short Orifice
1 / 0.75 NPT
Propeller
1 / 26
Direct / 1
5200
Short Orifice
1 / 0.75 NPT
Propeller
1 / 26
Direct / 1
5500
Short Orifice
1 / 0.75 NPT
Propeller
1 / 26
Direct / 1
5800
No. Motors / kW (HP)
Motor RPM
1 / 0.30 (0.40)
950
1 / .56 (0.75)
950
1 / .56 (0.75)
950
1 / .56 (0.75)
950
1 / .56 (0.75)
950
Belt Drive Indoor Fan -Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Fan Diameter xWidth - mm (in.)
DrvieType / No. Speeds
No. Motors
280 X 280 (11 x 11)
Belt /Variable Speed
1
305 X 305 (12 x 12)
Belt /Variable Speed
1
305 X 305 (12 x 12)
Belt /Variable Speed
1
381 X 381 (15 x 15)
Belt /Variable Speed
1
381 X 381 (15 x 15)
Belt /Variable Speed
1
Standard Motor Power - kW (HP)
Oversized Motor Power - kW (HP)
Motor RPM - Standard / Oversized
Motor Frame Size
1.1 (1.5)
1.1 (1.5)
1.5 (2.0)
1450 / 1450
56
1.5 (2.0)
2.2 (3.0)
1450 / 2850
56
1.5 (2.0)
2.2 (3.0)
1450 / 2850
56
2.2 (3.0)
-
-
1450 / -
56
2850 / -
56
Filters - Type Furnished
(No.) Size Reccommended - mm
(No.) Size Reccommended - in.
Refrigerant Charge - kg (lbs) of R-22 4
Throwaway
(2) 508 X 762 X 25
(2) 20 X 30 X 1
3.7 (8.2)
Throwaway
(4) 406 X 635 X 50
(4) 16 X 25 X 2
3.7 (8.2)
Throwaway
(4) 406 X 635 X 50
(4) 16 X 25 X 2
4.5 (10.0)
Throwaway
(4) 508 X 635 X 50
(4) 20 X 25 X 2
Circuit 1 - 3.8 (8.3)
Circuit 2 - 2.0 (4.4)
Throwaway
(4) 508 X 635 X 50
(4) 20 X 25 X 2
Circuit 1 - 3.4 (7.5)
Circuit 2 - 3.3 (7.3)
Notes:
1. Cooling Performance is rated at 35.0 C (95 F) ambient, 26.7 C (80 F) entering dry bulb, 19.4 C (67 F) entering wet bulb. Gross capacity does not include the effect of fan motor
heat. Net capacity includes the effect of fan motor heat. Units are suitable for operation to 20 % of nominal airflow.
2. EER are rated at ARI conditions.
3. Outdoor Sound rating shown is tested in accordance with ARI Standard 270. For more information refer to Performance Data Table "Sound Power Level".
4. Refrigerant charge is an approcimate value. For a more precise value, see unit nameplate and service literature.
RT-PRC016-EN
13
Performance
Data
Table PD-1 — Gross Cooling Capacities (kW) -TSC060AD - (SI)
Ambient Temperature (C)
Enter.
Dry
Bulb
30
35
40
45
19
Entering Wet Bulb Temperature (C)
19 22 16 19
m3/h
Temp
16
19
22
16
22
16
22
Airflow (C)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
16.2 13.9 18.5 11.3 19.9 8.3 15.0 13.3 17.4 11.3 19.3 8.0 13.9 12.7 16.1 10.7 18.4 7.5 12.7 12.1 14.7 9.5 17.3 7.0
16.7 16.7 18.6 14.1 20.0 11.1 15.8 15.8 17.4 13.6 19.4 10.8 14.8 14.8 16.1 13.0 18.5 10.3 13.8 13.8 14.7 12.3 17.3 9.8
18.1 18.1 18.7 16.9 20.2 13.6 17.2 17.2 17.7 16.5 19.5 13.5 16.2 16.2 16.5 15.9 18.5 13.1 15.1 15.1 15.1 15.1 17.3 12.6
19.3 19.3 19.2 19.2 20.3 16.2 18.5 18.5 18.5 18.5 19.6 16.1 17.6 17.6 17.6 17.6 18.7 15.9 16.6 16.6 16.6 16.6 17.5 15.4
16.7 14.8 18.8 11.8 20.1 8.6 15.5 14.2 17.8 11.3 19.5 8.3 14.2 13.5 16.5 11.4 18.7 7.7 13.1 12.9 15.0 10.8 17.6 7.2
17.5 17.5 18.9 14.9 20.2 11.4 16.5 16.5 17.8 14.4 19.6 11.2 15.4 15.4 16.5 13.8 18.8 10.8 14.4 14.4 15.1 13.1 17.6 10.3
18.8 18.8 19.1 17.9 20.4 14.1 17.9 17.9 18.2 17.6 19.7 14.1 16.9 16.9 17.0 17.0 18.8 13.8 15.8 15.8 15.8 15.8 17.7 13.4
19.8 19.8 19.8 19.8 20.6 16.8 19.2 19.2 19.2 19.2 19.9 16.9 18.3 18.3 18.3 18.3 19.0 16.8 17.4 17.4 17.4 17.4 17.9 16.4
17.1 15.6 19.1 12.3 20.2 8.8 15.9 15.0 18.1 11.8 19.7 8.5 14.6 14.3 16.8 11.2 18.9 7.9 13.4 13.4 15.3 11.4 17.8 7.5
18.1 18.1 19.2 15.5 20.4 11.6 17.1 17.1 18.2 15.1 19.8 11.5 16.0 16.0 16.9 14.6 19.0 11.3 14.9 14.9 15.4 13.9 17.9 10.8
19.3 19.3 19.5 18.7 20.6 14.5 18.5 18.5 18.6 18.6 20.0 14.6 17.6 17.6 17.6 17.6 19.1 14.4 16.5 16.5 16.5 16.5 17.9 14.1
20.2 20.2 20.2 20.2 20.8 17.4 19.6 19.6 19.6 19.6 20.2 17.6 18.9 18.9 18.9 18.9 19.3 17.6 18.0 18.0 18.0 18.0 18.3 17.4
17.4 16.4 19.3 12.6 20.3 9.1 16.2 15.8 18.4 12.2 19.8 8.8 14.9 14.9 17.1 11.7 19.0 8.1 13.9 13.9 15.5 12.1 18.0 7.7
18.6 18.6 19.4 16.1 20.5 12.3 17.7 17.7 18.4 15.8 19.9 11.8 16.6 16.6 17.2 15.3 19.1 11.6 15.4 15.4 15.8 14.6 18.1 11.2
19.7 19.7 19.7 19.4 20.7 14.9 19.0 19.0 19.0 19.0 20.1 15.0 18.1 18.1 18.1 18.1 19.3 15.0 17.1 17.1 17.1 17.1 18.2 14.7
20.5 20.5 20.5 20.5 20.9 17.9 20.0 20.0 20.0 20.0 20.4 18.2 19.3 19.3 19.3 19.3 19.5 18.3 18.4 18.4 18.4 18.4 18.6 18.2
24
27
30
3060
33
24
27
3400
30
33
24
27
3740
30
33
24
27
4080
30
33
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-1a — Gross Cooling Capacities (MBH) _ TSC060AD _ (IP)
Ambient Temperature (F)
Enter.
Dry
Bulb
85
95
105
115
67
Entering Wet Bulb Temperature (F)
67 73 61 67
CFM
Temp
61
67
73
61
73
61
73
Airflow (F)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
56.1 47.1 64.4 37.0 68.8 25.1 51.6 44.7 60.6 36.7 66.9 23.9 47.0 42.4 55.6 34.5 64.0 22.6 42.4 40.1 50.2 30.3 60.0 20.8
57.3 56.5 64.6 45.8 69.3 34.2 53.3 53.3 60.7 43.9 67.3 32.9 49.5 49.5 55.7 41.6 64.2 31.4 45.7 45.7 50.4 39.2 60.1 29.6
61.3 61.3 64.9 54.5 69.7 42.0 57.7 57.7 61.0 52.9 67.6 41.4 53.9 53.9 56.3 50.7 64.4 40.3 50.0 50.0 51.2 48.3 60.2 38.4
65.0 65.0 65.8 63.3 70.4 49.7 62.1 62.1 62.4 62.2 68.0 49.7 58.5 58.5 58.5 58.5 64.6 48.8 54.4 54.4 54.4 54.4 60.3 47.2
57.5 49.8 65.4 38.5 69.3 25.5 53.0 47.5 61.8 38.7 67.5 24.4 48.3 45.1 56.9 36.6 64.7 23.0 43.7 42.8 51.3 34.2 60.9 21.4
59.3 59.3 65.6 47.9 69.8 35.4 55.7 55.7 62.0 46.4 68.0 34.2 51.6 51.6 57.1 44.1 65.0 32.7 47.7 47.7 51.5 41.6 61.0 30.9
63.6 63.6 66.0 57.3 70.5 43.1 60.3 60.3 62.5 56.2 68.3 43.0 56.4 56.4 58.0 54.1 65.2 42.1 52.2 52.2 52.8 51.7 61.2 40.6
66.9 66.9 67.2 66.5 71.1 51.4 64.4 64.4 64.4 64.4 68.9 51.8 61.0 61.0 61.0 61.0 65.6 51.3 57.1 57.1 57.1 57.1 61.5 50.1
58.8 52.5 66.1 39.8 69.6 25.9 54.3 50.2 62.8 38.1 67.9 24.9 49.4 47.8 58.0 38.6 65.3 23.4 44.8 44.8 52.2 36.2 61.6 21.7
61.5 61.5 66.4 49.8 70.3 36.8 57.8 57.8 63.0 48.6 68.3 35.0 53.6 53.6 58.2 46.5 65.6 33.9 49.4 49.4 52.6 44.0 61.8 32.2
65.4 65.4 67.0 59.8 71.0 44.6 62.4 62.4 63.7 59.2 69.0 44.3 58.7 58.7 59.4 57.4 66.0 43.8 54.3 54.3 54.3 54.3 62.0 42.5
68.4 68.4 68.4 68.4 71.7 52.8 66.1 66.1 66.1 66.1 69.6 53.6 63.1 63.1 63.0 63.0 66.4 53.6 59.3 59.3 59.3 59.3 62.4 52.7
60.0 55.1 66.6 40.8 70.0 26.4 55.5 52.8 63.6 39.6 68.3 25.3 50.6 50.4 59.0 37.4 65.7 24.0 46.2 46.2 53.1 38.2 62.2 22.1
63.2 63.2 67.1 51.4 70.7 37.7 59.6 59.6 63.8 50.7 68.8 35.8 55.4 55.4 59.2 48.8 66.2 35.0 51.1 51.1 53.5 46.3 62.4 33.4
66.7 66.7 67.8 62.0 71.5 45.3 64.1 64.1 64.8 61.9 69.5 45.5 60.5 60.5 60.8 60.6 66.6 45.2 56.3 56.3 56.2 56.2 62.7 44.3
69.5 69.5 69.5 69.5 72.1 54.1 67.4 67.4 67.4 67.4 70.2 55.3 64.6 64.6 64.5 64.5 67.1 55.7 61.1 61.1 61.0 61.0 63.2 55.1
75
80
85
1800
90
75
80
2000
85
90
75
80
2200
85
90
75
80
2400
85
90
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC016-EN
14
Performance
Data
Table PD-2 — Gross Cooling Capacities (kW) -TSC072AD - (SI)
Ambient Temperature (C)
Enter.
Dry
Bulb
30
35
19
40
45
19
Entering Wet Bulb Temperature (C)
22 16 19
m3/h
Temp
16
19
22
16
22
16
22
Airflow (C)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
20.9 17.5 23.3 14.6 24.6 10.3 19.7 16.8 22.4 13.6 24.0 9.9 18.4 16.1 21.2 12.9 23.2 9.4 17.1 15.4 19.7 12.9 22.0 9.0
21.6 21.2 23.4 17.4 24.8 13.5 20.4 20.4 22.5 17.0 24.1 13.3 19.4 19.4 21.2 16.4 23.3 12.8 18.2 18.2 19.8 15.7 22.1 12.3
22.9 22.9 23.6 20.6 25.0 16.5 22.1 22.1 22.7 20.4 24.3 16.3 21.0 21.0 21.5 19.9 23.5 16.1 19.9 19.9 20.2 19.2 22.2 15.6
24.0 24.0 24.1 23.8 25.2 19.4 23.4 23.4 23.3 23.3 24.5 19.3 22.5 22.5 22.4 22.4 23.6 19.3 21.4 21.4 21.4 21.4 22.3 18.8
21.5 18.5 23.6 15.2 24.8 10.6 20.3 17.9 22.8 14.2 24.2 10.1 19.0 17.2 21.6 13.6 23.4 9.8 17.6 16.4 20.1 12.9 22.3 9.3
22.3 22.3 23.8 18.1 25.1 14.5 21.3 21.3 22.9 17.9 24.3 13.6 20.2 20.2 21.6 17.3 23.6 13.4 19.0 19.0 20.2 16.6 22.4 12.8
23.6 23.6 24.0 21.6 25.3 17.6 22.9 22.9 23.2 21.5 24.6 16.8 21.8 21.8 22.0 21.1 23.7 16.7 20.7 20.7 20.8 20.5 22.5 16.3
24.6 24.6 24.6 24.6 25.5 20.0 23.9 23.9 23.9 23.9 24.8 20.1 23.1 23.1 23.1 23.1 23.9 20.1 22.1 22.1 22.1 22.1 22.7 19.8
22.0 19.5 23.9 15.8 25.0 10.7 20.8 18.9 23.1 14.7 24.4 10.4 19.5 18.2 21.9 14.2 23.5 10.1 18.1 17.4 20.5 13.5 22.5 9.6
22.9 22.9 24.0 18.7 25.3 13.9 22.1 22.1 23.2 18.6 24.5 13.9 20.9 20.9 22.0 18.2 23.7 13.6 19.7 19.7 20.6 17.6 22.6 13.3
24.1 24.1 24.3 22.4 25.5 17.4 23.4 23.4 23.5 22.4 24.8 17.3 22.5 22.5 22.5 22.2 23.9 17.2 21.3 21.3 21.3 21.3 22.8 17.0
25.0 25.0 25.0 25.0 25.7 20.7 24.4 24.4 24.4 24.4 25.1 20.8 23.7 23.7 23.7 23.7 24.2 20.8 22.6 22.6 22.6 22.6 23.1 20.7
22.4 20.3 24.1 16.3 25.2 10.9 21.2 19.8 23.2 15.1 24.5 10.7 19.9 19.1 22.2 14.7 23.6 10.3 18.5 18.4 20.8 14.0 22.7 9.9
23.4 23.4 24.3 19.3 25.5 14.5 22.6 22.6 23.4 19.2 24.7 14.7 21.5 21.5 22.3 19.0 23.8 14.0 20.3 20.3 20.9 18.4 22.8 13.7
24.5 24.5 24.6 23.2 25.6 17.8 23.8 23.8 23.9 23.2 25.0 17.8 23.0 23.0 23.0 23.0 24.1 17.7 21.8 21.8 21.8 21.8 23.0 17.7
25.4 25.4 25.4 25.4 25.9 21.2 24.8 24.8 24.8 24.8 25.3 21.4 24.1 24.1 24.1 24.1 24.4 21.4 23.1 23.1 23.1 23.1 23.4 21.6
24
27
30
3670
33
24
27
4080
30
33
24
27
4490
30
33
24
27
4900
30
33
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-2a — Gross Cooling Capacities (MBH) -TSC072AD - (IP)
Ambient Temperature (F)
Enter.
Dry
Bulb
85
95
105
115
67
Entering Wet Bulb Temperature (F)
67 73 61 67
CFM
Temp
61
67
73
61
73
61
73
Airflow (F)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
72.2 59.1 80.6 47.1 85.1 31.0 67.5 56.5 77.7 44.1 82.7 29.6 62.6 53.9 73.0 41.8 79.9 28.0 57.4 51.2 67.5 39.2 75.5 26.0
73.8 70.7 81.0 56.1 85.8 42.2 69.4 68.2 77.9 55.0 83.4 40.7 65.0 65.0 73.1 52.6 80.4 39.0 60.6 60.6 67.6 50.0 75.8 36.8
77.7 77.7 81.4 66.3 86.3 51.7 74.3 74.3 78.2 65.6 83.8 50.1 70.3 70.3 73.6 63.5 80.7 49.2 66.0 66.0 68.3 61.0 76.1 47.4
81.3 81.3 82.4 76.3 87.1 59.8 78.8 78.8 79.4 76.0 84.6 59.4 75.1 75.1 75.3 74.6 81.3 59.0 70.8 70.8 70.7 70.7 76.6 57.4
74.2 62.5 81.6 49.2 85.7 31.5 69.3 59.9 78.7 46.0 83.4 30.1 64.4 57.3 74.2 43.7 80.2 28.5 59.1 54.6 68.9 41.1 76.3 26.6
76.1 75.0 82.1 58.2 86.5 43.7 72.1 72.1 79.0 57.4 84.2 42.1 67.9 67.9 74.4 55.4 80.9 40.4 63.3 63.3 69.0 53.0 76.8 38.4
80.0 80.0 82.6 69.1 86.8 52.8 77.1 77.1 79.5 68.7 84.7 51.6 73.1 73.1 75.3 67.3 81.4 50.7 68.7 68.7 70.1 65.0 77.2 49.4
83.3 83.3 83.8 79.7 87.1 61.5 80.7 80.7 80.9 79.4 85.5 61.5 77.5 77.5 77.5 77.5 82.1 61.1 73.3 73.3 73.3 73.3 77.8 60.2
75.8 65.6 82.3 50.7 86.2 32.0 71.0 63.2 79.4 49.8 84.0 30.7 66.0 60.6 75.4 45.6 80.7 29.0 60.6 57.8 70.0 42.9 77.0 27.2
78.1 78.1 82.9 60.1 87.2 44.1 74.6 74.6 79.8 59.4 84.7 44.3 70.3 70.3 75.6 58.1 81.2 41.3 65.7 65.7 70.1 55.7 77.6 39.8
81.7 81.7 83.6 71.6 88.2 54.0 79.1 79.1 80.5 71.3 85.4 53.6 75.4 75.4 76.6 70.7 82.0 52.1 70.9 70.9 71.6 68.7 78.1 51.3
84.8 84.8 85.0 82.5 89.1 62.3 82.3 82.3 82.3 82.3 86.1 61.2 79.4 79.4 79.4 79.4 82.8 63.0 75.2 75.2 75.2 75.2 78.7 62.8
77.0 68.3 82.9 52.2 86.6 32.5 72.5 66.4 80.0 51.4 84.5 31.2 67.5 63.7 76.2 47.1 81.2 29.5 62.1 61.0 70.8 44.7 77.6 27.8
79.6 79.6 83.7 61.8 87.6 44.7 76.6 76.6 80.6 61.3 85.4 44.0 72.4 72.4 76.5 60.5 81.8 42.1 67.7 67.7 71.1 58.2 78.1 40.9
83.0 83.0 84.4 73.9 88.7 54.9 80.4 80.4 81.5 73.9 86.2 54.1 77.1 77.1 77.8 73.8 82.7 53.5 72.7 72.7 72.9 71.9 78.8 53.0
85.9 85.9 86.0 85.0 89.6 65.2 83.6 83.6 83.6 83.6 87.0 63.2 81.0 81.0 81.0 81.0 83.5 65.0 76.8 76.8 76.8 76.8 79.5 65.3
75
80
85
2160
90
75
80
2400
85
90
75
80
2640
85
90
75
80
2880
85
90
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC016-EN
15
Performance
Data
Table PD-3 — Gross Cooling Capacities (kW) -TSC090AD - (SI)
Ambient Temperature (C)
Enter.
Dry
Bulb
30
35
40
45
19
Entering Wet Bulb Temperature (C)
19 22 16 19
m3/h
Temp
16
19
22
16
22
16
22
Airflow (C)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24.5 21.6 26.9 17.1 28.1 12.0 22.7 20.6 25.8 16.3 27.7 11.5 20.8 19.6 24.1 15.4 26.8 11.0 19.0 18.7 22.0 14.8 25.6 10.3
25.4 25.4 27.1 21.1 28.5 15.9 24.1 24.1 25.9 20.8 27.8 15.9 22.5 22.5 24.3 20.0 27.0 15.5 20.9 20.9 22.2 19.0 25.7 14.8
27.0 27.0 27.4 25.3 28.7 19.5 26.0 26.0 26.4 25.3 28.1 19.7 24.8 24.8 25.0 24.8 27.1 19.6 23.2 23.2 23.1 23.1 25.8 19.2
28.1 28.1 28.1 28.1 29.0 23.3 27.5 27.5 27.5 27.5 28.4 23.6 26.5 26.5 26.5 26.5 27.4 23.9 25.3 25.3 25.3 25.3 26.1 23.6
25.1 23.0 27.2 18.1 28.4 12.4 23.4 22.1 26.2 17.1 27.8 11.9 21.4 21.1 24.6 16.8 27.1 11.3 19.7 19.7 22.5 15.3 25.9 10.7
26.3 26.3 27.4 22.0 28.6 16.3 25.1 25.1 26.4 22.0 28.0 16.2 23.6 23.6 24.9 21.4 27.2 16.0 21.9 21.9 22.8 20.4 26.0 15.6
27.6 27.6 27.8 26.4 29.0 20.2 26.8 26.8 27.0 26.8 28.3 20.4 25.7 25.7 25.7 25.7 27.4 20.6 24.3 24.3 24.3 24.3 26.2 20.4
28.6 28.6 28.6 28.6 29.3 24.1 28.1 28.1 28.1 28.1 28.7 24.6 27.3 27.3 27.3 27.3 27.8 25.0 26.2 26.2 26.2 26.2 26.6 25.1
25.6 24.2 27.4 18.4 28.4 12.5 24.0 23.5 26.5 18.3 28.0 12.2 22.0 22.0 25.1 17.1 27.3 11.7 20.4 20.4 22.9 16.2 26.2 11.1
26.9 26.9 27.7 22.8 28.8 16.5 25.9 25.9 26.8 23.0 28.3 16.7 24.5 24.5 25.4 22.7 27.4 16.5 22.8 22.8 23.5 21.8 26.3 16.3
28.0 28.0 28.1 27.3 29.1 20.6 27.4 27.4 27.4 27.4 28.7 21.2 26.5 26.5 26.4 26.4 27.7 21.4 25.2 25.2 25.2 25.2 26.5 21.4
28.9 28.9 28.9 28.9 29.5 24.7 28.5 28.5 28.5 28.5 29.1 25.6 27.8 27.8 27.8 27.8 28.1 26.0 26.8 26.8 26.8 26.8 27.0 26.3
26.1 25.4 27.6 18.5 28.5 12.7 24.5 24.5 26.7 19.1 28.1 12.5 22.8 22.8 25.4 18.0 27.4 12.0 21.1 21.1 23.4 17.0 26.3 11.4
27.3 27.3 27.9 23.4 28.9 16.8 26.5 26.5 27.1 23.9 28.5 17.1 25.3 25.3 25.8 23.8 27.7 17.0 23.6 23.6 24.1 23.1 26.5 16.9
28.3 28.3 28.4 28.1 29.2 21.0 27.8 27.8 27.8 27.8 28.8 21.8 27.0 27.0 27.0 27.0 27.9 22.1 25.8 25.8 25.8 25.8 26.8 22.3
29.1 29.1 29.1 29.1 29.6 25.2 28.8 28.8 28.8 28.8 29.3 26.4 28.2 28.2 28.2 28.2 28.4 26.9 27.3 27.3 27.3 27.3 27.4 27.4
24
27
30
4590
33
24
27
5100
30
33
24
27
5610
30
33
24
27
6120
30
33
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-3a — Gross Cooling Capacities (MBH) -TSC090AD - (IP)
Ambient Temperature (F)
Enter.
Dry
Bulb
85
95
105
115
67
Entering Wet Bulb Temperature (F)
67 73 61 67
CFM
Temp
61
67
73
61
73
61
73
Airflow (F)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
84.4 72.7 92.7 55.2 96.6 35.6 77.7 69.1 89.4 52.6 95.2 34.0 70.4 65.4 83.4 50.6 92.5 32.0 63.7 61.9 75.3 46.9 88.2 29.8
86.5 86.5 93.3 67.5 97.8 48.9 81.2 81.2 89.6 66.8 96.2 48.4 75.1 75.1 83.8 64.0 93.1 46.6 69.4 69.4 75.8 60.3 88.5 44.1
91.5 91.5 94.2 80.6 98.9 59.9 87.7 87.7 90.6 80.8 97.2 60.5 82.5 82.5 85.1 78.8 93.5 59.5 76.4 76.4 77.7 75.2 88.8 58.1
95.1 95.1 95.7 93.2 100.0 71.0 92.6 92.6 92.5 92.5 97.5 71.8 88.7 88.7 88.7 88.7 94.3 72.6 83.7 83.7 83.6 83.6 89.5 71.8
86.5 77.3 93.5 56.9 97.1 36.1 80.0 73.9 90.6 56.4 95.8 34.6 72.6 70.1 85.2 52.3 93.2 32.7 65.6 65.6 76.9 49.9 89.1 30.5
89.4 89.4 94.3 70.0 98.3 52.8 84.9 84.9 91.0 70.2 96.9 49.4 78.8 78.8 85.6 68.2 93.9 48.9 72.7 72.7 77.8 64.5 89.6 46.3
93.6 93.6 95.4 83.8 99.4 61.1 90.6 90.6 92.2 85.2 98.0 62.3 86.1 86.1 87.3 84.2 94.5 61.9 80.1 80.1 80.1 80.1 90.0 61.2
96.8 96.8 97.0 96.7 100.5 72.8 94.8 94.8 94.8 94.8 99.0 75.4 91.5 91.5 91.4 91.4 95.4 75.8 87.0 87.0 87.0 87.0 90.9 75.9
88.1 81.3 94.3 59.1 97.5 36.7 82.1 78.5 91.4 58.6 96.2 35.2 74.1 74.1 86.4 54.8 93.7 33.4 68.1 68.1 78.5 51.2 89.8 31.2
91.4 91.4 95.1 72.1 98.7 50.2 87.6 87.6 92.1 73.3 97.4 50.3 82.2 82.2 87.1 72.0 94.5 49.7 75.6 75.6 79.7 68.7 90.4 48.3
95.1 95.1 96.2 86.6 99.8 62.1 92.7 92.7 93.6 89.0 98.5 63.8 88.8 88.8 89.2 89.1 95.2 64.0 83.5 83.5 83.5 83.5 90.9 63.9
97.9 97.9 97.9 97.9 101.0 74.3 96.4 96.4 96.3 96.3 99.7 77.5 93.5 93.5 93.5 93.5 96.3 78.6 89.4 89.4 89.4 89.4 92.1 79.5
89.5 85.0 95.1 60.6 97.8 37.2 84.0 83.1 92.2 60.7 96.6 35.7 76.7 76.7 87.5 57.3 94.1 34.0 70.4 70.4 80.0 53.8 90.4 31.9
92.9 92.9 95.6 74.0 99.0 50.8 89.7 89.7 93.0 76.0 97.8 51.0 84.8 84.8 88.3 75.6 95.2 50.9 78.1 78.1 81.6 72.8 90.9 49.5
96.2 96.2 96.9 88.9 100.2 63.1 94.2 94.2 94.7 92.3 99.0 65.1 90.7 90.7 90.7 90.7 95.8 65.8 86.0 86.0 86.0 86.0 91.7 66.3
98.7 98.7 98.7 98.7 101.3 75.7 97.5 97.5 97.5 97.5 100.1 79.4 94.9 94.9 94.9 94.9 97.0 81.1 91.2 91.2 91.2 91.2 93.0 82.7
75
80
85
2700
90
75
80
3000
85
90
75
80
3300
85
90
75
80
3600
85
90
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC016-EN
16
Performance
Data
Table PD-4 — Gross Cooling Capacities (kW) -TSC102AD - (SI)
Ambient Temperature (C)
Enter.
Dry
Bulb
30
35
40
45
19
Entering Wet Bulb Temperature (C)
19 22 16 19
m3/h
Temp
16
19
22
16
22
16
22
Airflow (C)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
28.0 24.3 31.5 19.5 33.4 14.1 26.0 23.3 30.0 18.7 32.5 13.5 23.9 22.2 27.8 17.7 31.3 12.9 21.6 21.6 25.4 17.3 29.7 12.2
29.0 28.4 31.6 24.3 33.6 18.7 27.4 27.1 30.1 23.6 32.7 18.5 25.6 25.6 28.0 22.7 31.4 17.8 23.9 23.9 25.6 21.6 29.8 17.1
31.0 31.0 31.9 29.0 33.9 23.0 29.7 29.7 30.5 28.6 32.9 22.8 28.1 28.1 28.1 28.1 31.5 22.5 26.3 26.3 26.5 25.7 29.9 22.0
32.6 32.6 32.7 32.1 34.1 27.3 31.6 31.6 31.6 31.4 33.2 27.3 30.4 30.4 30.3 30.3 31.8 27.2 28.9 28.9 28.8 28.8 30.2 26.8
28.8 25.8 31.9 20.4 33.6 14.4 26.8 24.8 30.5 19.6 32.8 13.9 24.2 24.2 28.5 18.7 31.6 13.4 22.5 22.5 26.0 17.6 30.1 12.6
30.1 29.8 32.1 25.4 34.0 19.2 28.6 28.6 30.7 25.0 32.9 19.1 26.8 26.8 28.8 24.2 31.7 18.6 25.0 25.0 26.3 23.1 30.2 17.9
32.0 32.0 32.5 30.5 34.2 23.7 30.9 30.9 30.9 30.9 33.2 23.7 29.4 29.4 29.4 29.4 31.9 23.6 27.6 27.6 27.7 27.2 30.3 23.2
33.4 33.4 33.4 33.2 34.5 28.1 32.6 32.6 32.5 32.5 33.6 28.5 31.4 31.4 31.4 31.4 32.3 28.5 30.0 30.0 30.0 30.0 30.8 28.3
29.5 27.3 32.2 21.1 33.8 14.7 27.6 26.3 31.0 20.5 33.0 14.4 25.1 25.1 29.1 19.6 31.8 13.8 23.5 22.9 26.5 18.5 30.4 12.9
31.0 31.0 32.5 26.5 34.2 19.7 29.7 29.7 31.2 26.3 33.3 19.5 27.9 27.9 29.4 25.6 32.0 19.2 26.0 26.0 27.0 24.5 30.5 18.7
32.7 32.7 33.0 31.7 34.6 24.5 31.7 31.7 31.7 31.7 33.6 24.6 30.4 30.4 30.5 29.9 32.3 24.5 28.8 28.8 28.8 28.6 30.7 24.3
34.0 34.0 34.0 34.0 34.8 28.9 33.2 33.2 33.2 33.2 33.9 29.5 32.1 32.1 32.1 32.1 32.7 29.7 30.9 30.9 30.9 30.9 31.3 29.7
30.1 28.7 32.5 21.7 33.9 15.1 27.9 27.9 31.3 21.4 33.1 14.7 26.0 26.0 29.3 20.4 32.2 14.2 24.2 23.9 27.0 19.4 30.6 13.3
31.7 31.7 32.8 27.4 34.4 20.0 30.5 30.5 31.6 27.4 33.4 20.0 28.8 28.8 29.8 26.9 32.3 19.7 26.9 26.9 27.6 25.9 30.7 19.4
33.2 33.2 33.2 33.2 34.8 25.0 32.3 32.3 32.4 31.7 33.7 25.2 31.2 31.2 31.2 30.9 32.6 25.4 29.7 29.7 29.7 29.7 31.0 25.3
34.4 34.4 34.4 34.4 35.2 30.0 33.7 33.7 33.7 33.7 34.2 30.4 32.9 32.9 32.9 32.9 33.1 30.8 31.5 31.5 31.5 31.5 31.4 31.4
24
27
30
5200
33
24
27
5780
30
33
24
27
6360
30
33
24
27
6940
30
33
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-4a — Gross Cooling Capacities (MBH) -TSC102AD - (IP)
Ambient Temperature (F)
Enter.
Dry
Bulb
85
95
105
115
67
Entering Wet Bulb Temperature (F)
67 73 61 67
CFM
Temp
61
67
73
61
73
61
73
Airflow (F)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
96.7 81.9 109.1 63.4 115.0 42.2 89.1 78.1 104.0 60.7 112.1 40.4 81.2 74.1 96.3 59.2 107.9 38.3 73.7 70.3 87.0 55.2 102.4 35.8
98.2 98.2 109.4 78.3 116.1 58.1 92.7 90.8 104.2 76.3 113.0 56.2 85.7 85.2 96.6 72.9 108.5 53.9 79.3 79.3 87.4 68.8 102.7 51.3
105.0 105.0 110.2 93.1 117.3 70.8 100.0 100.0 105.0 91.8 113.6 70.4 93.6 93.6 98.0 88.8 108.9 68.7 86.8 86.8 89.2 84.7 103.1 66.7
110.4 110.4 111.6 107.4 118.0 84.0 106.5 106.5 106.4 106.4 114.4 83.5 101.4 101.4 101.7 99.6 109.6 83.1 94.8 94.8 94.9 94.6 103.5 81.6
99.3 87.0 110.2 65.9 115.6 42.9 91.8 83.2 105.8 63.7 112.9 41.1 83.6 79.1 98.7 60.6 108.8 39.0 75.2 75.2 89.0 58.6 103.4 36.5
102.5 100.4 110.9 81.6 116.9 59.2 96.7 95.9 106.0 80.4 113.8 58.8 89.7 89.7 99.0 77.4 109.6 56.1 82.9 82.9 89.7 73.3 103.9 53.5
108.4 108.4 111.9 97.4 118.2 72.7 104.1 104.1 107.2 97.0 114.6 72.7 98.2 98.2 100.8 94.9 110.1 71.5 91.0 91.0 91.0 91.0 104.2 70.0
113.2 113.2 113.1 113.1 119.5 86.5 109.7 109.7 109.9 107.6 115.6 86.6 105.1 105.1 105.1 104.4 111.0 86.9 99.4 99.4 99.2 99.2 105.1 86.0
101.6 91.8 111.3 67.8 116.2 43.6 94.3 88.2 107.1 66.5 113.5 41.8 84.7 84.7 100.4 63.0 109.5 39.6 78.4 76.4 90.9 59.0 104.2 37.1
105.4 104.4 112.1 84.5 117.6 60.0 100.3 100.3 107.4 84.0 114.7 59.4 93.4 93.4 100.9 81.6 110.0 57.9 86.1 86.1 91.7 77.7 104.8 55.6
111.0 111.0 113.3 101.2 118.9 74.2 107.0 107.0 108.9 101.7 116.0 74.8 101.8 101.8 101.8 101.8 111.2 73.8 94.9 94.9 94.9 94.9 105.3 72.9
115.2 115.2 115.2 115.2 120.3 88.6 112.1 112.1 112.1 111.1 116.5 89.3 107.8 107.8 107.7 107.7 112.1 90.2 102.6 102.6 102.6 102.6 106.4 90.0
103.5 96.3 112.1 69.5 116.6 43.8 94.9 94.9 107.9 68.7 114.0 42.5 87.5 87.5 101.8 65.6 110.0 40.3 80.7 79.5 92.4 61.7 104.8 37.8
107.9 107.9 113.0 87.1 118.1 60.8 103.1 103.1 108.6 87.3 115.3 60.3 96.8 96.8 102.5 85.6 110.7 59.5 89.1 89.1 93.7 82.0 105.4 57.5
112.9 112.9 114.4 104.5 119.5 75.5 109.3 109.3 110.4 105.7 116.7 76.5 104.5 104.5 104.5 104.5 111.9 76.7 98.2 98.2 98.6 96.7 106.2 75.5
116.7 116.7 116.7 116.7 120.9 90.6 113.9 113.9 113.8 113.8 117.9 92.9 109.9 109.9 109.8 109.8 113.0 93.2 104.9 104.9 104.9 104.9 107.5 93.5
75
80
85
3060
90
75
80
3400
85
90
75
80
3740
85
90
75
80
4080
85
90
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC016-EN
17
Performance
Data
Table PD-5 — Gross Cooling Capacities (kW) -TSC120AD - (SI)
Ambient Temperature (C)
Enter.
Dry
Bulb
30
35
40
45
19
Entering Wet Bulb Temperature (C)
19 22 16 19
m3/h
Temp
16
19
22
16
22
16
22
Airflow (C)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
31.9 28.6 35.3 22.8 37.2 15.9 29.6 27.4 33.6 21.7 36.5 15.4 27.1 26.2 31.0 20.5 35.2 14.8 24.6 24.6 28.4 19.9 33.2 14.0
33.4 33.4 35.5 28.2 37.7 21.4 31.6 31.6 33.9 27.8 36.7 21.4 29.5 29.5 31.3 26.6 35.3 20.7 27.5 27.5 28.9 25.5 33.3 19.9
35.5 35.5 36.0 33.8 38.1 26.5 34.2 34.2 34.5 33.8 37.0 26.7 32.3 32.3 32.2 32.2 35.5 26.6 30.4 30.4 30.4 30.4 33.4 25.9
37.1 37.1 37.1 37.1 38.5 31.6 36.2 36.2 36.2 36.2 37.3 31.9 34.8 34.8 34.8 34.8 35.9 32.3 33.2 33.2 33.2 33.2 34.0 31.8
32.7 30.4 35.7 23.8 37.5 16.3 30.5 29.3 34.2 22.8 36.8 15.9 27.8 27.8 31.9 21.8 35.5 15.3 25.7 25.7 29.0 21.2 33.7 14.5
34.5 34.5 36.0 29.5 38.0 21.9 32.9 32.9 34.5 29.4 37.0 22.0 30.9 30.9 32.3 28.5 35.7 21.7 28.7 28.7 29.7 27.4 33.8 21.0
36.3 36.3 36.6 35.4 38.4 27.4 35.3 35.3 35.3 35.3 37.3 27.6 33.7 33.7 33.7 33.7 35.9 27.8 31.8 31.8 31.7 31.7 34.0 27.5
37.9 37.9 37.8 37.8 38.9 32.8 37.0 37.0 37.0 37.0 37.8 33.3 35.9 35.9 35.9 35.9 36.5 33.9 34.4 34.4 34.4 34.4 34.7 33.8
33.5 32.2 36.0 24.7 37.8 16.9 31.1 31.1 34.7 23.9 37.0 16.3 28.9 28.9 32.4 22.9 35.8 15.7 26.6 26.6 29.6 22.5 34.1 14.9
35.3 35.3 36.4 30.6 38.2 22.4 34.0 34.0 35.0 30.8 37.4 22.7 32.0 32.0 33.0 30.2 36.0 22.5 29.9 29.9 30.5 29.1 34.2 22.0
37.0 37.0 37.0 37.0 38.7 28.1 36.1 36.1 36.1 36.1 37.9 28.9 34.7 34.7 34.7 34.7 36.4 29.1 32.9 32.9 32.9 32.9 34.5 29.0
38.4 38.4 38.3 38.3 39.2 33.7 37.7 37.7 37.7 37.7 38.4 34.9 36.7 36.7 36.7 36.7 37.0 35.4 35.3 35.3 35.3 35.3 35.3 35.3
33.9 33.9 36.3 24.9 37.9 17.3 32.0 32.0 35.0 25.6 37.5 16.1 29.8 29.8 32.8 23.9 36.1 16.2 27.5 27.5 29.8 23.6 34.4 15.3
35.9 35.9 36.7 31.7 38.5 22.8 34.8 34.8 35.5 32.2 37.7 23.2 32.9 32.9 33.6 31.9 36.3 23.2 30.6 30.6 30.6 30.6 34.5 23.0
37.5 37.5 37.5 37.5 38.9 28.8 36.7 36.7 36.7 36.7 38.1 29.8 35.5 35.5 35.5 35.5 36.7 30.2 33.7 33.7 33.7 33.7 34.9 30.5
38.8 38.8 38.7 38.7 39.5 34.6 38.4 38.4 38.2 38.2 38.7 36.1 37.3 37.3 37.3 37.3 37.4 36.7 36.0 36.0 36.0 36.0 36.0 36.0
24
27
30
6120
33
24
27
6800
30
33
24
27
7480
30
33
24
27
8160
30
33
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-5a — Gross Cooling Capacities (MBH) -TSC120AD - (IP)
Ambient Temperature (F)
Enter.
Dry
Bulb
85
95
105
115
67
Entering Wet Bulb Temperature (F)
67 73 61 67
CFM
Temp
61
67
73
61
73
61
73
Airflow (F)
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
109.9 96.4 122.1 73.8 128.5 47.6 101.2 92.1 116.7 70.3 125.9 45.7 91.8 87.5 107.7 67.7 121.6 43.4 82.1 82.1 97.2 63.2 115.0 40.9
113.5 113.5 122.6 90.4 129.9 65.7 106.6 106.6 117.1 89.2 127.2 65.0 99.0 99.0 108.4 85.4 122.2 62.4 91.0 91.0 98.2 81.0 115.2 59.7
120.2 120.2 123.8 108.0 131.3 80.9 115.2 115.2 118.5 107.9 127.8 81.5 108.1 108.1 110.5 104.9 122.6 80.6 100.3 100.3 100.3 100.3 115.4 78.4
125.4 125.4 125.4 125.4 132.7 96.3 121.8 121.8 121.8 121.8 128.7 97.3 116.4 116.4 116.4 116.4 123.6 98.2 109.2 109.2 109.2 109.2 116.4 97.0
112.7 102.4 123.1 75.6 129.3 48.4 104.2 98.3 118.5 73.6 126.9 46.6 93.7 93.7 109.9 70.9 122.7 44.3 85.6 85.6 99.3 67.2 116.5 41.9
117.3 117.3 124.1 94.1 130.8 66.9 111.1 111.1 119.0 94.0 128.2 66.8 103.5 103.5 110.8 90.8 123.5 65.3 95.2 95.2 100.8 86.6 116.8 62.5
123.2 123.2 125.6 112.8 132.3 82.9 119.0 119.0 120.8 114.1 129.5 84.5 112.5 112.5 112.5 112.5 124.1 84.2 104.9 104.9 104.8 104.8 117.1 83.0
127.9 127.9 127.9 127.9 133.8 99.2 124.9 124.9 124.9 124.9 130.8 102.4 120.2 120.2 120.2 120.2 125.3 103.1 113.9 113.9 113.8 113.8 118.4 102.9
115.1 108.2 124.5 77.5 130.0 49.2 107.0 104.4 119.8 77.6 127.6 47.4 97.3 97.3 111.7 73.2 123.6 45.2 88.7 88.7 101.1 71.1 117.6 42.7
120.1 120.1 125.3 97.3 131.6 67.9 114.9 114.9 120.6 98.4 129.0 68.2 107.3 107.3 112.9 96.1 124.5 68.1 98.9 98.9 103.1 92.0 118.0 65.1
125.5 125.5 127.0 116.9 133.1 84.7 121.9 121.9 122.8 119.6 130.5 87.0 116.4 116.4 116.3 116.3 125.3 88.0 108.7 108.7 108.7 108.7 118.4 87.0
130.0 130.0 129.7 129.7 134.7 101.8 127.3 127.3 127.2 127.2 131.9 105.9 123.0 123.0 123.0 123.0 126.7 107.5 117.2 117.2 117.2 117.2 120.2 108.4
117.1 113.2 125.5 81.7 130.6 50.0 108.8 108.8 120.8 80.6 128.3 48.2 100.5 100.5 113.2 76.3 124.3 46.1 91.6 91.6 102.7 72.1 118.5 43.6
122.3 122.3 126.5 100.7 132.2 68.9 117.8 117.8 122.0 102.4 129.8 69.5 110.5 110.5 114.9 101.3 125.7 69.3 102.2 102.2 105.2 97.3 119.0 67.7
127.2 127.2 128.4 121.1 133.8 86.3 124.1 124.1 124.1 124.1 131.2 89.2 119.0 119.0 119.0 119.0 126.5 90.9 112.0 112.0 112.0 112.0 119.7 90.9
131.3 131.3 131.5 131.5 135.4 104.2 129.3 129.3 129.0 129.0 132.8 108.9 125.2 125.2 125.2 125.2 127.8 111.4 119.8 119.8 119.8 119.8 121.7 113.3
75
80
85
3600
90
75
80
4000
85
90
75
80
4400
85
90
75
80
4800
85
90
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC016-EN
18
Performance
Data
Table PD-6 — Belt Drive Evaporator Fan Performance -TSC060AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
1.12 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
175
RPM
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
1.12 Nom kW Standard Motor & Drive
0.49 985 0.54 1023 0.59 1060 0.64
0.58 1028 0.64 1067 0.70 1104 0.76
2720
3060
3400
3740
4080
-
-
703
760
821
885
950
0.27
0.35
0.46
0.60
0.76
757
815
873
930
990
0.31
0.40
0.51
0.65
0.80
806
861
918
977
0.35
0.45
0.57
0.71
854
904
958
0.39
0.49
0.62
899
947
998
0.43
0.54
0.67
944
988
706
773
840
909
0.32
0.43
0.56
0.71
1036 0.71 1073 0.76 1111 0.82 1147 0.89
1089 0.88 1124 0.93 1158 0.98 1191 1.03
1143 1.06 1177 1.12 1209 1.17 1241 1.23
1016 0.77
1074 0.93
1053 0.82
1110 1.00
1034 0.87
External Static Pressure (Pascals)
300 325 350
RPM RPM
275
RPM
375
RPM
CFM
kW
RPM
kW
kW
kW
kW
1.12 Nom kW Standard Motor & Drive
2720
3060
3400
3740
4080
Notes:
1093 0.69
1138 0.82
1182 0.96
1226 1.10
1272 1.29
1126 0.74
1171 0.87
1215 1.02
1258 1.17
1160 0.79
1203 0.93
1246 1.09
1290 1.25
1190 0.84
1232 0.98
1276 1.15
1222 0.90
1262 1.04
1306 1.21
1.12 Nom kW Standard Motor &
Hi Static Drive
←
-
-
-
-
-
-
-
-
-
-
-
-
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
Table PD-6a — Belt Drive Evaporator Fan Performance -TSC060AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive
1-1/2 HP Standard Motor & Drive
1600
1800
2000
2200
2400
-
-
703
760
821
885
950
0.36
0.47
0.62
0.80
1.02
757
815
873
930
990
0.41
0.54
0.69
0.87
1.08
806
861
918
977
0.47
0.60
0.76
0.95
854
904
958
1016 1.03
1074 1.25
0.52
0.66
0.83
899
947
998
1053 1.10
1110 1.34
0.58
0.72
0.90
944
988
0.65
985
0.73 1023 0.79 1060 0.86
706
773
840
909
0.42
0.57
0.75
0.96
0.78 1028 0.86 1067 0.94 1104 1.02
1036 0.96 1073 1.02 1111 1.10 1147 1.19
1089 1.17 1124 1.24 1158 1.31 1191 1.39
1143 1.419 1177 1.50 1209 1.57 1241 1.65
1034 1.16
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
1-1/2 HP Standard Motor & Drive
1600
1800
2000
2200
2400
Notes:
1093 0.92
1138 1.10
1182 1.28
1226 1.48
1272 1.73
1126 0.99
1171 1.17
1215 1.37
1258 1.57
1160 1.06
1203 1.25
1246 1.46
1290 1.67
1190 1.13
1232 1.32
1276 1.54
1222 1.20
1262 1.39
1306 1.62
1-1/2 HP Standard Motor &
Hi Static Drive
←
-
-
-
-
-
-
-
-
-
-
-
-
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
RT-PRC016-EN
19
Performance
Data
Table PD-7 - Belt Drive Evaporator Fan Performance-TSC060AD - Horizontal Configuration - (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
125
RPM
150
RPM
1.12 Nom kW Standard Motor & Drive
175
RPM
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
1.12 Nom kW Std Motor & Low Static Drive
2720
3060
3400
3740
4080
707
778
850
923
997
0.26
0.36
0.48
0.63
0.80
774
840
908
978
0.31
0.41
0.54
0.69
837
897
961
1028 0.76
1096 0.94
0.37
0.48
0.60
898
953
1012 0.67
1075 0.83
1140 1.02
0.43
0.54
953
0.48
1001 0.54
1058 0.67
1111 0.81
1166 0.99
1223 1.18
1045 0.59 1087 0.65 1129 0.71 1168 0.77
1102 0.73 1143 0.79 1181 0.85 1219 0.92
1157 0.88 1198 0.95 1237 1.02 1274 1.09
1211 1.06 1254 1.14 1294 1.22 1330 1.29
1008 0.60
1062 0.74
1120 0.91
1183 1.10
1049 0.87
1266 1.27
-
-
-
-
-
-
1.12 Nom kW Standard Motor & Hi Static Drive
External Static Pressure (Pascals)
300 325 350
RPM RPM RPM
275
RPM
375
RPM
CFM
kW
kW
kW
kW
kW
1.12 Nom kW Standard Motor & Drive
2720
3060
3400
3740
4080
1206 0.83
1256 0.99
1309 1.16
1241 0.89
1291 1.05
1343 1.24
1275 0.96
1326 1.12
1376 1.31
1306 1.02
1359 1.19
1338 1.09
1390 1.26
1.12 Nom kW Standard Motor &
Hi Static Drive
←
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
Table PD-7a - Belt Drive Evaporator Fan Performance-TSC060AD - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor &
Low Static Drive
1-1/2 HP Standard Motor & Drive
1600
1800
2000
2200
2400
707
778
850
923
997
0.35
0.48
0.65
0.84
1.07
774
840
908
978
0.42
0.56
0.73
0.93
837
897
961
1028 1.02
1096 1.27
0.50
0.64
0.81
898
953
1012 0.90
1075 1.12
1140 1.37
0.57
0.72
953
0.65
1001 0.72
1058 0.89
1111 1.09
1166 1.32
1223 1.59
1045 0.80 1087 0.87 1129 0.95 1168 1.03
1008 0.81
1062 1.00
1120 1.22
1183 1.48
1102 0.98 1143 1.06 1181 1.15 1219 1.23
1157 1.19 1198 1.28 1237 1.37 1274 1.47
1211 1.43 1254 1.53 1294 1.63 1330 1.74
1049 1.17
1266 1.70
-
-
-
-
-
-
1-1/2 HP Standard Motor & Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
CFM
RPM BHP
1/2 HP Standard Motor & Drive
1-1/2 HP Standard Motor & Hi Static Drive
1600
1800
2000
2200
2400
1206 1.12
1256 1.32
1309 1.56
1241 1.20
1291 1.41
1343 1.66
1275 1.28
1326 1.50
1376 1.76
1306 1.37
1359 1.60
1338 1.46
1390 1.69
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
RT-PRC016-EN
20
Performance
Data
Table PD-8 — Belt Drive Evaporator Fan Performance -TSC072AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
1.12 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
1.12 Nom kW Standard Motor & Drive
175
RPM
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
3260
3670
4080
4490
4890
-
-
-
-
-
-
-
-
573
602
635
670
706
0.25
0.31
0.38
0.47
0.58
630
656
682
715
749
0.30
0.37
0.45
0.54
0.64
680
706
732
758
789
0.36
0.43
0.51
0.60
0.71
726
751
777
802
830
0.41
0.49
0.58
0.68
0.79
769
792
818
845
870
0.47
0.55
0.64
0.75
0.87
811
832
856
883
909
0.52
0.61
0.71
0.82
0.95
851 0.58
871 0.67
893 0.77
919 0.89
945 1.02
889 0.65
908 0.74
930 0.84
953 0.96
979 1.10
548
584
621
660
0.26
0.33
0.42
0.51
569
612
0.35
0.45
1.12 Nom kW Standard Motor
& Hi Static Drive
External Static Pressure (Pascals)
300 325 350
RPM RPM
275
RPM
375
RPM
CFM
kW
RPM
kW
kW
kW
kW
1.12 Nom kW Std Motor
& Drive
1.12 Nom kW Standard Motor
& Hi Static Drive
3260
3670
4080
4490
4890
925
944
964
986
0.71
0.81
0.91
1.04
960
978
998
1019 1.11
1043 1.26
0.77
0.87
0.99
994
0.83
1026 0.89
1043 1.01
1063 1.14
1082 1.27
1103 1.42
1057 0.95
1073 1.08
1092 1.21
1112 1.35
1133 1.51
1010 0.94
1030 1.06
1051 1.19
1073 1.34
1011 1.18
1.50 Nom kW Over-Sized Motor
& Hi Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
TestedTo Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
Table PD-8a — Belt Drive Evaporator Fan Performance -TSC072AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor
&
Low Static Drive
1-1/2 HP Standard Motor
&
Drive
0.70
0.81
0.95
1.10
1.27
1920
2160
2400
2640
2880
-
-
-
-
-
-
573
602
635
670
706
0.34
0.42
0.52
0.64
0.78
630
656
682
715
749
0.41
0.50
0.60
0.72
0.86
680
706
732
758
789
0.48
0.58
0.69
0.81
0.96
726
751
777
802
830
0.55
0.65
0.77
0.91
1.06
769
792
818
845
870
0.62
0.73
0.86
1.01
1.16
811
851 0.78
871 0.90
893 1.04
919 1.20
945 1.37
889 0.87
908 0.99
930 1.13
953 1.29
979 1.48
548
584
621
660
0.35
0.45
0.56
0.69
832
856
883
909
-
-
569
612
0.47
0.60
1-1/2 HP Standard Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
RPM BHP
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
CFM
1-1/2 HP Standard Mtr
& Drive
1920
2160
2400
2640
2880
925
944
964
986
0.95
1.08
1.22
1.39
960
978
998
1019 1.49
1043 1.69
1.03
1.17
1.32
994
1.11
1026 1.19
1043 1.36
1063 1.53
1082 1.71
1103 1.90
1057 1.27
1073 1.44
1092 1.63
1112 1.81
1133 2.02
1-1/2 HP Standard Motor
Hi Static Drive
&
1010 1.26
1030 1.42
1051 1.60
1073 1.79
←
1011 1.58
2 HP Over-Sized Mtr & Hi Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
RT-PRC016-EN
21
Performance
Data
Table PD-9 — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
Low Static Drive
125
RPM
150
RPM
1.12 Nom kW Standard Motor
175
RPM
200
RPM
Drive
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
&
kW
kW
kW
kW
kW
kW
1.12 Nom kW Standard Motor
&
3260
3670
4080
4490
4890
-
-
565
609
660
710
762
0.23
0.31
0.40
0.51
0.64
627
663
701
745
795
0.29
0.36
0.45
0.56
0.70
679
716
751
788
828
0.34
0.42
0.51
0.62
0.76
726
762
798
833
869
0.39
0.48
0.59
0.69
0.82
771
804
839
875
911
0.45
0.54
0.65
0.77
0.91
814
843
877
914
950
0.51
0.60
0.71
0.85
0.99
857
883
914
949
986
0.57
0.67
0.78
0.91
899 0.63
922 0.74
950 0.85
939 0.70
960 0.81
984 0.93
566
619
672
726
0.26
0.35
0.45
0.58
984 0.98 1016 1.06
1.07 1019 1.14 1051 1.22
1.12 Nom kW Standard Motor
& Hi Static Drive
1.12 Nom kW Standard Motor
&
Drive
External Static Pressure (Pascals)
300 325 350
RPM RPM RPM
275
RPM
375
RPM
CFM
kW
kW
kW
kW
kW
1.12 Nom kW Standard Motor & Hi Static Drive
3260
3670
4080
4490
4890
978
996
1020 1.00
1049 1.14
1081 1.30
0.76
0.87
1015 0.83
1034 0.95
1055 1.08
1081 1.23
1112 1.38
1051 0.90
1069 1.02
1089 1.16
1113 1.31
1141 1.47
1086 0.97
1103 1.09
1122 1.23
1144 1.40
1170 1.57
1118 1.04
1136 1.17
1154 1.31
1176 1.48
1199 1.66
1.50 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
Table PD-9a — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive
1-1/2 HP Standard Motor
&
Drive
1920
2160
2400
2640
2880
-
-
565
609
660
710
762
0.31
0.41
0.54
0.68
0.86
627
663
701
745
795
0.39
0.48
0.60
0.76
0.94
679
716
751
788
828
0.45
0.57
0.69
0.83
1.02
726
762
798
833
869
0.52
0.64
0.78
0.93
1.11
771
804
839
875
911
0.60
0.72
0.87
1.04
1.21
814
843
877
914
950
0.69
857
883
914
949
986
0.77
0.90
1.04
1.22
899 0.85
922 0.99
950 1.14
939 0.93
960 1.08
984 1.24
566
619
672
726
0.35
0.47
0.61
0.77
0.80
0.95
1.13
1.33
984 1.31 1016 1.42
1.44 1019 1.53 1051 1.63
1-1/2 HP Standard Motor
&
Drive
1-1/2 HP Std Motor & Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
CFM
RPM BHP
1-1/2 HP Standard Motor
&
Hi Static Drive
1920
2160
2400
2640
2880
978
996
1020 1.35
1049 1.53
1081 1.74
1.02
1.17
1015 1.11
1034 1.27
1055 1.45
1081 1.65
1112 1.86
1051 1.20
1069 1.36
1089 1.55
1113 1.76
1141 1.97
1086 1.30
1103 1.46
1122 1.66
1144 1.87
1170 2.10
1118 1.39
1136 1.56
1154 1.76
1176 1.98
1199 2.22
2 HP Over-Sized Motor
&
High Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
RT-PRC016-EN
22
Performance
Data
Table PD-10 — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
1.50 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
175
RPM
1.50 Nom kW Standard Motor
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
&
Drive
4080
4590
5100
5610
6120
-
-
-
-
-
-
-
-
-
-
-
-
701
743
789
836
885
0.47
0.59
0.74
0.92
1.14
750
787
827
873
921
0.54
0.66
0.82
1.00
1.22
794
830
867
908
954
0.60
0.74
0.90
1.08
1.30
834
871
906
944
986
0.67
0.82
0.98
1.17
873
908
944
980
0.73
0.89
1.06
909 0.80
943 0.96
980 1.15 1013 1.23
945 0.87
977 1.04
699
747
797
848
0.53
0.68
0.85
1.06
703
755
809
0.61
0.77
0.96
713
771
0.69
0.88
1.26 1016 1.35 1050 1.45
1.39 1019 1.49 1052 1.58 1085 1.69
1.50 Nom kW Standard Motor
& Hi Static Drive
External Static Pressure (Pascals)
300 325 350
RPM RPM
275
RPM
375
RPM
CFM
kW
RPM
kW
kW
kW
kW
1.50 Nom kW Std Motor
& Drive
1.50 Nom kW Standard Motor
& Hi Static Drive
4080
4590
5100
5610
6120
980
0.95
1013 1.02
1043 1.19
1076 1.39
1111 1.63
1148 1.89
1046 1.10
1074 1.27
1105 1.47
1141 1.72
1177 1.99
1076 1.17
1105 1.36
1134 1.56
1168 1.80
1204 2.08
1106 1.25
1134 1.44
1163 1.65
1197 1.90
1232 2.18
1010 1.11
1045 1.31
1081 1.54
1116 1.79
2.24 Nom kW Over-Sized Motor
& Hi Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-10a — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
RPM BHP RPM BHP RPM BHP RPM BHP
Drive
.80
.90
1.00
CFM
RPM BHP
2 HP Standard Motor
RPM BHP
RPM BHP
Low Static Drive
RPM BHP
RPM BHP
RPM BHP
&
2 HP Standard Motor
&
2400
2700
3000
3300
3600
-
-
-
-
-
-
-
-
-
-
-
-
701
743
789
836
885
0.63
0.79
0.99
1.24
1.53
750
787
827
873
921
0.72
0.89
1.10
1.34
1.63
794
830
867
908
954
0.81
0.99
1.20
1.45
1.74
834
871
906
944
986
0.90
1.09
1.31
1.57
873
908
944
980
0.98
1.19
1.43
909 1.08
943 1.29
980 1.54 1013 1.65
945 1.17
977 1.39
699
747
797
848
0.70
0.91
1.15
1.42
703
755
809
0.81
1.03
1.29
713
771
0.93
1.19
1.69 1016 1.82 1050 1.94
1.87 1019 1.99 1052 2.13 1085 2.26
2 HP Standard Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
RPM BHP
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
CFM
2 HP Standard Mtr
& Drive
2 HP Standard Motor &
Hi Static Drive
2400
2700
3000
3300
3600
980
1.27
1010 1.49
1045 1.76
1081 2.06
1116 2.39
1013 1.37
1046 1.47
1076 1.57
1105 1.82
1134 2.09
1168 2.42
1204 2.79
1106 1.68
1043 1.60
1076 1.87
1111 2.18
1148 2.53
1074 1.71
1105 1.98
1141 2.30
1177 2.66
1134 1.93
1163 2.21
1197 2.55
1232 2.93
3 HP Over-Sized Mtr & Hi Static Drive
Notes:
Data Includes Pressure Drop DueTo Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
RT-PRC016-EN
23
Performance
Data
Table PD-11 — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
125
RPM
150
RPM
1.50 Nom kW Standard Motor
175
RPM
200
RPM
Drive
225
RPM kW
250
RPM kW
m3/h
1.50 Nom kW Std Motor & Low Static Drive
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
&
4080
4590
5100
5610
6120
-
-
673
738
805
873
942
0.42
0.56
0.74
0.96
1.22
718
773
837
903
970
0.47
0.62
0.81
1.03
1.30
769
817
870
930
996
0.54
0.68
0.87
1.10
1.37
814
862
912
963
0.61
0.76
0.94
1.17
855
904
951
1000 1.25
1052 1.52
0.67
0.85
1.03
893
941
989
0.73
0.92
929
975
0.81
965 0.88
999 0.96
702
771
842
913
0.51
0.68
0.89
1.14
0.98 1009 1.06 1041 1.14
1.12 1025 1.21 1056 1.28 1088 1.36
1037 1.34 1073 1.45 1106 1.55 1136 1.63
1086 1.61 1121 1.71 1153 1.82 1184 1.93
1021 1.45
1.50 Nom kW Standard Motor
&
Drive
1.50 Nom kW Standard Motor &
Hi Static Drive
2.24 Nom kW OS
Motor & Hi Static Drive
External Static Pressure (Pascals)
300 325 350
RPM RPM RPM
1.50 Nom kW Standard Motor & Hi Static Drive
275
RPM
375
RPM kW
CFM
kW
kW
kW
kW
4080
4590
5100
5610
6120
1035 1.04
1073 1.22
1117 1.44
1165 1.72
1215 2.04
1070 1.12
1104 1.31
1146 1.53
1194 1.80
1242 2.13
1104 1.19
1136 1.40
1176 1.62
1220 1.88
1269 2.22
1137 1.27
1167 1.48
1205 1.72
1248 1.98
1295 2.31
1168 1.35
1198 1.57
1233 1.82
1275 2.08
1319 2.40
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-11a — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
RPM BHP RPM BHP RPM BHP RPM BHP
Drive
.80
.90
1.00
CFM
RPM BHP
2 HP Std Motor & Low Static Drive
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
2 HP Standard Motor
&
2400
2700
3000
3300
3600
-
-
673
738
805
873
942
0.56
0.76
1.00
1.29
1.63
718
773
837
903
970
0.63
0.83
1.08
1.38
1.74
769
817
870
930
996
0.72
0.92
1.17
1.47
1.84
814
862
912
963
0.82
1.02
1.26
1.57
855
904
951
1000 1.68
1052 2.04
0.90
1.13
1.38
893
941
989
0.98
1.23
929
975
1.08
965 1.18
999 1.29
702
771
842
913
0.68
0.91
1.19
1.53
1.32 1009 1.42 1041 1.52
1.51 1025 1.62 1056 1.72 1088 1.82
1037 1.80 1073 1.94 1106 2.08 1136 2.19
1086 2.16 1121 2.29 1153 2.44 1184 2.59
1021 1.94
2 HP Standard Motor
&
Drive
2 HP Std Motor & Hi Static Drive
3 HP Over-Sized Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
RPM BHP
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
CFM
2 HP Standard Motor
&
Hi Static Drive
2400
2700
3000
3300
3600
1035 1.39
1073 1.64
1117 1.93
1165 2.30
1215 2.73
1070 1.50
1104 1.76
1146 2.05
1194 2.41
1242 2.86
1104 1.60
1136 1.87
1176 2.17
1220 2.52
1269 2.98
1137 1.70
1167 1.99
1205 2.31
1248 2.66
1295 3.10
1168 1.81
1198 2.11
1233 2.44
1275 2.79
1319 3.22
3 HP Over-Sized Motor
&
High Static Drive
Notes:
Data Includes Pressure Drop DueTo Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
TestedTo Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In OurTabular Data Will
Not Result In NuisanceTripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
RT-PRC016-EN
24
Performance
Data
Table PD-12 — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
1.50 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
175
RPM
1.50 Nom kW Standard Motor
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
&
Drive
4620
5200
5780
6350
6930
-
-
-
-
-
-
-
-
-
-
-
-
613
650
689
729
770
0.45
0.55
0.68
0.82
0.98
655
688
724
764
804
0.54
0.64
0.76
0.92
1.09
695
725
759
795
834
0.62
0.73
0.86
1.01
1.19
733
761
792
826
864
0.71
0.83
0.96
1.11
1.30
769
796
825
857
892
0.81
0.93
1.07
1.22
1.40
802 0.90
828 1.03
856 1.18
887 1.34
920 1.52
833 1.00
861 1.13
887 1.28
916 1.46
948 1.64
611
651
693
738
0.48
0.59
0.72
0.89
612
659
706
0.51
0.64
0.80
622
671
0.56
0.71
1.50 Nom kW Standard
Motor & Hi Static Drive
External Static Pressure (Pascals)
375 400
RPM RPM
1.50 Nom kW Std Mtr & Hi Static Dr
275
RPM
1.50 Nom kW Std Mtr & Drive
300
RPM
325
RPM
350
RPM
425
RPM
450
RPM
475
RPM kW
500
RPM kW
m3/h
kW
kW
kW
kW
kW
kW
kW
kW
4620
5200
5780
6350
6930
863
891
917
945
976
1.11
1.24
1.40
1.58
1.78
892
919
946
974
1.21
1.35
1.51
1.70
920
946
974
1001 1.82
1029 2.04
1.33
1.46
1.63
946
973
1001 1.75
1028 1.95
1055 2.17
1.44
1.58
973
999
1026 1.88
1054 2.08
1081 2.30
1.55
1.71
999
1.67
1025 1.79 1050 1.90 1073 2.02 1098 2.14
1048 1.96 1072 2.09 1096 2.22 1119 2.34
1074 2.14 1099 2.27 1121 2.41 1143 2.55
1103 2.34 1126 2.48 1148 2.62 1170 2.76
1130 2.58 1154 2.72 1176 2.85 1199 3.01
1024 1.83
1051 2.01
1079 2.20
1105 2.43
1002 1.91
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-12a — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
RPM BHP RPM BHP RPM BHP RPM BHP
Drive
769
.80
.90
1.00
CFM
RPM BHP
RPM BHP
2 HP Standard Motor
RPM BHP
Low Static Drive
RPM BHP
RPM BHP
RPM BHP
&
2 HP Standard Motor
&
2720
3060
3400
3740
4080
-
-
-
-
-
-
-
-
-
-
-
-
613
650
689
729
770
0.60
0.74
0.91
1.10
1.32
655
688
724
764
804
0.72
0.85
1.02
1.23
1.46
695
725
759
795
834
0.84
0.98
1.15
1.35
1.60
733
761
792
826
864
0.95
1.11
1.29
1.49
1.74
1.08
1.25
1.43
1.64
1.88
802 1.21
828 1.38
856 1.58
887 1.79
920 2.04
833 1.34
861 1.52
887 1.72
916 1.96
948 2.20
611
651
693
738
0.64
0.79
0.97
1.19
796
825
857
892
612
659
706
0.68
0.86
1.08
622
671
0.76
0.96
2 HP Standard Motor &
Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
2 HP Standard Mtr & Drive
1.20
RPM BHP
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
1.60
RPM BHP
1.70
1.80
1.90
2.00
CFM
RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Motor & Hi Static Drive
2720
3060
3400
3740
4080
863
891
917
945
976
1.48
1.66
1.87
2.11
2.38
892
919
946
974
1.63
1.81
2.03
2.28
920
946
974
1001 2.44
1029 2.73
1.78
1.96
2.18
946
973
1001 2.34
1028 2.61
1055 2.91
1.93
2.12
973
999
1026 2.52
1054 2.78
1081 3.09
2.08
2.29
999
2.24
1025 2.39 1050 2.55 1073 2.71 1098 2.88
1048 2.63 1072 2.80 1096 2.98 1119 3.14
1074 2.86 1099 3.05 1121 3.23 1143 3.41
1103 3.14 1126 3.32 1148 3.51 1170 3.71
1130 3.45 1154 3.65 1176 3.83 1199 4.03
1024 2.46
1051 2.69
1079 2.96
1105 3.26
1002 2.56
3 HP Over-Sized Motor & Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
RT-PRC016-EN
25
Performance
Data
Table PD-13 — Belt Drive Evaporator Fan Performance -TSC102AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
125
RPM
150
RPM
175
RPM
1.50 Nom kW Standard Motor
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
1.50 Nom kW Std Mtr & Low Static Drive
&
Drive
4620
5200
5780
6350
6930
-
-
-
-
646
693
743
799
857
0.50
0.64
0.82
1.04
1.31
689
735
781
830
883
0.58
0.73
0.91
1.12
1.39
734
773
819
865
913
0.67
0.82
1.01
1.23
1.48
781
812
853
899
945
0.77
0.92
1.11
1.34
1.60
826
855
886
930
977
0.88
1.03
1.21
1.45
865
897
925
960
0.98
1.15
1.34
1.56
898 1.07
934 1.27
964 1.47 1000 1.60
994 1.68 1028 1.82
928 1.16
969 1.38
616
675
735
796
0.51
0.68
0.89
1.14
654
711
770
828
0.57
0.75
0.97
1.23
1.72 1006 1.84 1034 1.96 1061 2.08
1.50 Nom kW Std Mtr
& High Static Drive
2.24 Nom kW Over-Sized
Motor & High Static Drive
External Static Pressure (Pascals)
375 400
RPM RPM
275
RPM
300
RPM
325
RPM
350
RPM
425
RPM
450
RPM
475
RPM kW
500
RPM kW
m3/h
kW
kW
kW
kW
kW
kW
kW
kW
1.50 Nom kW Standard Motor & High Static Drive
4620
5200
5780
6350
6930
956
999
1034 1.73
1063 1.96
1093 2.23
1.25
1.49
982
1.33
1008 1.42
1052 1.68
1094 1.97
1129 2.26
1157 2.53
1033 1.51
1078 1.78
1120 2.08
1158 2.40
1188 2.70
1056 1.60
1101 1.88
1145 2.20
1185 2.53
1218 2.86
1079 1.69
1124 1.98
1168 2.31
1210 2.66
1245 3.01
1102 1.78 1125 1.87 1146 1.95 1168 2.04
1146 2.08 1168 2.18 1188 2.27 1209 2.37
1191 2.42 1213 2.53 1234 2.63 1254 2.74
1234 2.78 1256 2.90 1278 3.03 1299 3.15
1026 1.58
1067 1.86
1098 2.11
1125 2.38
1273 3.16 1297 3.31
-
-
-
-
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-13a — Belt Drive Evaporator Fan Performance -TSC102AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Mtr & Low Static Drive
2 HP Standard Motor
&
Drive
2720
3060
3400
3740
4080
-
-
-
-
646
693
743
799
857
0.67
0.86
1.10
1.40
1.76
689
735
781
830
883
0.78
0.98
1.22
1.51
1.86
734
773
819
865
913
0.90
1.10
1.36
1.65
1.99
781
812
853
899
945
1.04
1.23
1.49
1.79
2.15
826
855
886
930
1.18
1.39
1.62
1.94
865
897
925
960
1.31
1.55
1.79
2.09
898 1.44
934 1.70
964 1.97 1000 2.14
994 2.26 1028 2.44
928 1.56
969 1.85
616
675
735
796
0.69
0.92
1.20
1.53
654
711
770
828
0.77
1.01
1.30
1.65
977
2.30 1006 2.47 1034 2.63 1061 2.79
3 HP Over-Sized Mtr & Drive
2 HP Std Motor &
Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
2 HP Standard Motor
1.20
RPM BHP
1.30
RPM BHP
High Static Drive
1008 1.91
1052 2.26
1094 2.64
1129 3.03
1157 3.40
1.40
RPM BHP
1.50
RPM BHP
1.60
RPM BHP
1.70
RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Over-Sized Motor Drive
1102 2.38 1125 2.5 1146 2.62 1168 2.74
1146 2.79 1168 2.92 1188 3.05 1209 3.18
1191 3.24 1213 3.39 1234 3.53 1254 3.68
1234 3.73 1256 3.89 1278 4.06 1299 4.23
1.80
1.90
2.00
CFM
&
&
2720
3060
3400
3740
4080
956
999
1.67
1.99
982
1.79
1033 2.03
1078 2.39
1120 2.79
1158 3.21
1188 3.62
1056 2.14
1101 2.52
1145 2.94
1185 3.39
1218 3.83
1079 2.26
1124 2.66
1168 3.09
1210 3.56
1245 4.03
1026 2.12
1067 2.49
1098 2.84
1125 3.19
1034 2.32
1063 2.63
1093 2.99
1273 4.24 1297 4.44
-
-
-
-
3 HP Over-Sized Motor
&
Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
RT-PRC016-EN
26
Performance
Data
Table PD-14 — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
2.24 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
175
RPM
2.24 Nom kW Standard Motor
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
&
Drive
5440
6120
6800
7480
8160
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
718
764
814
864
916
0.72
0.90
1.11
1.36
1.64
754
797
844
894
945
0.82
0.99
1.21
1.48
1.77
789
829
874
922
972
0.93
1.10
1.32
1.59
1.90
822
860
903
948
997
1.03
1.22
1.44
1.70
856 1.14
892 1.34
932 1.56
887 1.25
922 1.46
960 1.69
731
782
834
887
0.81
1.01
1.24
1.52
715
773
833
0.81
1.04
1.31
747
803
861
0.90
1.14
1.42
741
803
0.95
1.21
975 1.82 1001 1.95
2.02 1022 2.14 1046 2.27
External Static Pressure (Pascals)
375 400
RPM RPM
275
RPM
300
RPM
325
RPM
350
RPM
425
RPM
450
RPM
475
RPM kW
500
RPM kW
m3/h
kW
kW
kW
kW
kW
kW
kW
kW
2.24 Nom kW Standard Motor & Drive
5440
6120
6800
7480
8160
917
951
988
1028 2.09
1071 2.41
1.36
1.57
1.82
945
979
1015 1.95
1053 2.23
1095 2.55
1.47
1.69
973
1.60
999
1.72
1024 1.84
1059 2.07
1093 2.35
1128 2.66
1166 3.02
1048 1.97
1082 2.20
1117 2.48
1152 2.81
1189 3.17
1072 2.10 1095 2.23 1117 2.37 1140 3.36
1107 2.34 1130 2.49 1152 2.63 1173 3.71
1142 2.63 1164 2.76 1187 2.91 1209 4.11
1007 1.82
1042 2.08
1078 2.38
1119 2.70
1033 1.94
1068 2.21
1103 2.52
1142 2.86
1176 2.95 1198 3.10 1221 3.25
1212 3.33
-
-
-
-
-
-
-
-
2.24 Nom kW Standard Motor & High Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-14a — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor Drive
.80
.90
1.00
CFM
RPM BHP
RPM BHP
3 HP Standard Motor
RPM BHP
RPM BHP
RPM BHP
RPM BHP
&
Low Static Drive
&
3200
3600
4000
4400
4800
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
718
764
814
864
916
0.97
1.20
1.49
1.82
2.20
754
797
844
894
945
1.10
1.33
1.63
1.98
2.38
789
829
874
922
972
1.25
1.48
1.77
2.13
2.55
822
860
903
948
997
1.38
1.63
1.93
2.28
856 1.53
892 1.79
932 2.09
887 1.67
922 1.95
960 2.27
731
782
834
887
1.08
1.35
1.67
2.04
715
773
833
1.09
1.40
1.76
747
803
861
1.21
1.53
1.90
741
803
1.27
1.62
975 2.44 1001 2.62
2.71 1022 2.87 1046 3.04
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
RPM BHP
3 HP Standard Motor & Drive
1.30
RPM BHP
1.40
1.50
RPM BHP
1.60
RPM BHP
1.70
1.80
1.90
2.00
CFM
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
3200
3600
4000
4400
4800
917
951
988
1028 2.81
1071 3.23
1.82
2.11
2.44
945
979
1015 2.62
1053 3.00
1095 3.42
1.97
2.27
973
2.14
999
2.30
1024 2.47
1059 2.78
1093 3.15
1128 3.57
1166 4.04
1048 2.65
1082 2.95
1117 3.33
1152 3.77
1189 4.25
1072 2.82 1095 3.00 1117 3.17 1140 3.36
1107 3.14 1130 3.33 1152 3.52 1173 3.71
1142 3.52 1164 3.70 1187 3.91 1209 4.11
1007 2.43
1042 2.79
1078 3.19
1119 3.62
1033 2.60
1068 2.97
1103 3.38
1142 3.83
1176 3.96 1198 4.15 1221 4.36
1212 4.46
-
-
-
-
-
-
-
-
3 HP Standard Motor & High Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
RT-PRC016-EN
27
Performance
Data
Table PD-15 — Belt Drive Evaporator Fan Performance -TSC120AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
2.24 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
175
RPM
2.24 Nom kW Standard Motor
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
&
Drive
1.28 965 1.41 1000 1.53
1.53 1002 1.67 1038 1.81
5440
6120
6800
7480
8160
-
-
691
761
833
905
977
0.67
0.91
1.22
1.58
2.02
730
792
860
931
0.75
0.99
1.29
1.67
771
829
890
955
0.84
1.08
1.38
1.75
807
865
923
983
0.94
1.19
1.50
1.86
844
898
956
1.04
1.30
1.62
886
930
986
1.16
1.41
926
965
729
802
876
950
0.84
1.13
1.49
1.91
1.73 1015 1.85 1044 1.98 1077 2.12
1014 1.99
1074 2.42
1045 2.12 1072 2.25 1098 2.37 1125 2.51
1102 2.56 1131 2.71 1156 2.84 1181 2.98
1002 2.11
1025 2.20
1048 2.30
2.24 Nom kW Standard Motor & High Static Drive
External Static Pressure (Pascals)
375 400
RPM RPM
275
RPM
300
RPM
325
RPM
350
RPM
425
RPM
450
RPM
475
RPM kW
500
RPM kW
m3/h
kW
kW
kW
kW
kW
kW
kW
kW
2.24 Nom kW Std Mtr & Drive
5440
6120
6800
7480
8160
1029 1.64
1072 1.95
1111 2.28
1152 2.65
1205 3.12
1057 1.75
1106 2.10
1143 2.43
1182 2.81
1229 3.27
1084 1.86
1134 2.22
1174 2.58
1211 2.97
1108 1.96
1160 2.35
1204 2.74
1241 3.14
1132 2.06
1185 2.47
1232 2.90
1270 3.31
1155 2.17
1209 2.59
1260 3.05
1177 2.27 1198 2.37 1219 2.48 1239 3.46
1231 2.70 1252 2.82 1274 2.94 1295 4.10
1283 3.18 1306 3.32
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.24 Nom kW Standard Motor & High Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-15a — Belt Drive Evaporator Fan Performance -TSC120AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
RPM BHP RPM BHP RPM BHP RPM BHP
Drive
926
965
2.32 1015 2.48 1044 2.65 1077 2.85
1045 2.84 1072 3.01 1098 3.18 1125 3.36
1102 3.43 1131 3.63 1156 3.81 1181 4.00
.80
.90
1.00
CFM
RPM BHP
3 HP Standard Motor & Low Static Drive
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
3 HP Standard Motor
&
3200
3600
4000
4400
4800
-
-
691
761
833
905
977
0.89
1.22
1.63
2.12
2.70
730
792
860
931
1.00
1.32
1.73
2.24
771
829
890
955
1.13
1.45
1.86
2.35
807
865
923
983
1.26
1.60
2.01
2.49
844
898
956
1014 2.66
1074 3.24
1.39
1.74
2.17
886
930
986
1.55
1.89
1.72
965 1.89 1000 2.06
2.06 1002 2.24 1038 2.43
729
802
876
950
1.13
1.52
1.99
2.56
1002 2.84
1025 2.96
1048 3.08
3 HP Standard Motor
&
High Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
3 HP Std Mtr & Drive
1.20
RPM BHP
1.30
RPM BHP
1.40
1.50
RPM BHP
1.60
RPM BHP
1.70
1.80
1.90
2.00
CFM
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
3200
3600
4000
4400
4800
1029 2.20
1072 2.62
1111 3.05
1152 3.55
1205 4.19
1057 2.35
1084 2.49
1134 2.98
1174 3.47
1211 3.99
1108 2.63
1160 3.15
1204 3.68
1241 4.21
1132 2.77
1185 3.31
1232 3.88
1270 4.44
1155 2.91
1209 3.47
1260 4.09
1177 3.05 1198 3.18 1219 3.32 1239 3.46
1231 3.63 1252 3.78 1274 3.94 1295 4.10
1106 2.81
1143 3.26
1182 3.76
1229 4.39
1283 4.27 1306 4.46
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 HP Standard Motor
&
High Static Drive
Notes:
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop DueTo Wet Coils And Filters.
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
RT-PRC016-EN
28
Performance
Data
Table PD-16 — Standard Motor & Sheave/Fan Speed (RPM)
Unit
6 Turns
Open
N/A
N/A
N/A
5 Turns
Open
898
698
752
4 Turns
Open
967
751
806
3 Turns
Open
1036
806
860
786
2 Turns
Open
1105
859
914
835
1 Turns
Open
1174
913
968
885
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Closed
1243
967
1020
934
N/A
N/A
688
782
737
838
894
950
1006
1062
Factory set at 3 turns open
Table PD-17 — Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (RPM)
Unit
6 Turns
Open
N/A
N/A
N/A
5 Turns
Open
691
537
671
4 Turns
Open
760
590
714
3 Turns
Open
829
644
757
2 Turns
Open
898
698
800
1 Turns
Open
967
752
843
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Closed
1036
806
886
811
N/A
N/A
629
717
664
754
701
799
737
844
773
885
922
Factory set at 3 turns open
Table PD-18 — Standard Motor & High Static Drive Accessory Sheave/Fan Speed (RPM)
Unit
6 Turns
Open
N/A
N/A
1020
936
5 Turns
Open
1243
967
1073
981
4 Turns
Open
1311
1021
1127
1032
1174
3 Turns
Open
1379
1075
1181
1083
1229
2 Turns
Open
1450
1128
1235
1134
1285
1 Turns
Open
1515
1183
1289
1182
1341
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Closed
1588
1235
N/A
N/A
N/A
1062
1118
Factory set at 3 turns open
Table PD-19 — Oversized Motor & Drive Sheave/Fan Speed (RPM)
Unit
6 Turns
Open
N/A
1112
N/A
5 Turns
Open
967
1182
971
4 Turns
Open
1021
1252
1041
N/A
3 Turns
Open
1075
1322
1111
N/A
2 Turns
Open
1128
1392
1181
N/A
1 Turns
Open
1183
1460
1251
N/A
Model No.
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Closed
1235
N/A
1321
N/A
N/A
N/A
Factory set at 3 turns open
Table PD-20 — Sound Power Level - dB (ref. 10 -12 Watts)
Unit
Octave Center Frequency
Overall
dBA
80
85
85
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Note:
63
84
83
83
83
83
125
91
90
90
89
86
250
79
86
86
84
80
500
77
82
83
81
77
1000
74
79
80
77
2000
71
4000
8000
63
63
64
62
68
70
71
69
66
75
75
72
69
83
79
73
60
Tests follow ARI 270-95
RT-PRC016-EN
29
Performance
Data
Table PD-21 — Static Pressure Drops Through Accessories - (Pascals)
Economizer
Electric Heater
OA/RA Dampers2
Accessory (kW)3
Unit
Model No.
TSC060AD
Airflow
(m3/h)
2720
3400
4080
3260
4080
4890
4080
5100
6120
4620
5780
6930
5440
6800
8160
Standard Pleated Filters
100% OA
100% RA
100% OA
100% RA
Filters1
25
(50 mm)
Downflow
Horizontal
9
11
17
25
-
13-27
13
21
30
5
40
-
-
-
-
37
30
46
64
25
27
33
27
35
52
31
47
75
42
65
85
11
17
26
2
5
10
30
46
64
15
20
25
20
30
62
22
45
77
35
75
87
4
6
9
5
5
10
5
12
20
10
15
22
12
20
25
37
55
55
72
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Notes:
10
17
15
22
-
8
-
22
30
-
13
-
15
22
5
-
8
-
25
32
12
17
7
15
17
12
17
22
-
-
-
16
25
6
-
-
-
35
45
12
20
20
27
-
-
-
-
10
15
9
14
20
-
-
10
17
26
30
40
17
25
27
37
40
50
-
1. Tested with standard filters. TheTSC060AD has 25 mm (1 inch) standard fiters. TheTSC072AD - 120AD has 50 mm (2 inch) standard filters.
The difference in pressure drop should be considered when utilizing optional 50 mm (2 inch) pleated filters.
2. OA = Outside Air and RA = Return Air
3. Nominal kW ratings at 415 V
Table PD-21a — Static Pressure Drops Through Accessories - (Inches of Water Column)
Economizer
Electric Heater
OA/RA Dampers2
Accessory (kW)3
Unit
Model No.
TSC060AD
Airflow
(CFM)
1600
2000
2400
1920
2400
2880
2400
3000
3600
2720
3400
4080
3200
4000
4800
Standard Pleated Filters
100% OA
100% RA
100% OA
100% RA
Filters1
0.10
0.15
0.22
0.04
0.06
0.09
0.06
0.10
0.14
0.05
0.08
0.12
0.07
0.11
0.16
(2 inch)
0.15
0.22
0.29
0.07
0.09
0.12
0.09
0.13
0.18
0.08
0.11
0.16
0.10
0.15
0.20
Downflow
Horizontal
9
13-27
0.053
0.083
0.120
0.021
0.034
0.052
0.034
0.063
0.102
0.026
0.041
0.059
0.036
0.056
0.081
40
-
-
-
-
-
-
-
-
-
-
-
0.12
0.18
0.26
0.10
0.11
0.13
0.11
0.14
0.21
0.12
0.19
0.30
0.17
0.26
0.34
0.04
0.07
0.10
0.01
0.02
0.04
0.02
0.05
0.07
0.03
0.06
0.07
0.05
0.07
0.09
0.12
0.18
0.26
0.06
0.08
0.10
0.08
0.12
0.25
0.09
0.18
0.31
0.14
0.30
0.35
0.01
0.02
0.04
0.02
0.02
0.04
0.02
0.05
0.08
0.04
0.06
0.09
0.05
0.08
0.10
0.045
0.070
0.100
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Notes:
-
-
-
-
-
-
-
-
-
-
-
-
-
0.042
0.070
0.106
1. Tested with standard filters. TheTSC060AD has 25 mm (1 inch) standard fiters. TheTSC072AD - 120AD has 50 mm (2 inch) standard filters.
The difference in pressure drop should be considered when utilizing optional 50 mm (2 inch) pleated filters.
2. OA = Outside Air and RA = Return Air
3. Nominal kW ratings at 415 V
Table PD-22 - Electric Heater Voltage Correction Factors (Apply to Auxiliary Electric Heat
Capacity)
Nominal
Voltage
Distribution
Voltage
380
Capacity
Multipiler
0.84
415
400
0.93
415
1.00
RT-PRC016-EN
30
Performance
Data
Table PD-23 — Auxiliary Electric Heat Capacity (SI)
Total2
Stage 1
Stage 2
Unit
Unit
Model No.
Voltage
KW
No. Stages
KW
KW
7.5 / 9.0
2
2
2
1
2
2
1
2
2
2
2
2
2
2
3.75 / 4.5
5.45 / 6.5
3.75 / 4.5
5.45 / 6.5
5.45 / 6.5
—-
5.6 / 6.7
11.3 / 13.5
—-
5.6 / 6.7
11.3 / 13.5
5.6 / 6.7
11.3 / 13.5
5.6 / 6.7
11.3 / 13.5
22.5 / 26.9
TSC060AD
TSC072AD
380-415/50/3
380-415/50/3
10.9 / 13.0
14.4 / 17.2
11.3 / 13.5
16.9 / 20.2
22.6 / 26.9
11.3 / 13.5
16.9 / 20.2
22.6 / 26.9
16.9 / 20.2
22.6 / 26.9
16.9 / 20.2
22.6 / 26.9
33.9 / 40.4
8.95 / 10.7
11.3 / 13.5
11.3 / 13.5
11.3 / 13.5
11.3 / 13.5
11.3 / 13.5
11.3 / 13.5
11.3 / 13.6
11.3 / 13.7
11.3 / 13.8
11.3 / 13.9
11.3 / 13.10
TSC090AD
TSC102AD
380-415/50/3
380-415/50/3
TSC120AD
380-415/50/3
Notes:
1. Does not include indoor fan power or heat
2. Heaters are rated at 380V / 415V. For other than rated voltage, CAP=(Voltage/Rated Voltage)2 x Rated Cap.
Table PD-23A — Auxiliary Electric Heat Capacity (IP)
Total2
Stage 1
Stage 2
Unit
Unit
Model No.
Voltage
MBH
26 / 31
38 / 45
50 / 59
39 / 47
58 / 69
78 / 92
39 / 47
58 / 69
78 / 92
58 / 69
78 / 92
58 / 69
78 / 92
116 / 138
No. Stages
MBH
MBH
13 / 16
19 / 23
19 / 23
—-
20 / 23
39 / 47
—-
20 / 23
39 / 47
20 / 23
39 / 47
20 / 23
39 / 47
77 / 92
2
2
2
1
2
2
1
2
2
2
2
2
2
2
13 / 16
19 / 23
31 / 37
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
TSC060AD
TSC072AD
380-415/50/3
380-415/50/3
TSC090AD
TSC102AD
380-415/50/3
380-415/50/3
TSC120AD
380-415/50/3
Notes:
1. Does not include indoor fan power or heat
2. Heaters are rated at 380 / 415V. For other than rated voltage, CAP=(Voltage/Rated Voltage)2 x Rated Cap.
RT-PRC016-EN
31
Performance
Data
Table PD-24 — Air Temperature Rise Across Electric Heaters (Degrees C)
kW
3400 m3/h
TSC060AD
6.6 / 7.9
9.6 / 11.4
—-
4100 m3/h
TSC072AD
—-
—-
8.3 / 9.9
—-
12.4 / 14.8
16.5 / 19.7
—-
5100 m3/h
TSC090AD
—-
—-
6.6 / 7.9
—-
9.9 / 11.8
13.2 / 15.7
—-
5800 m3/h
TSC102AD
—-
6800 m3/h
TSC120AD
—-
380V / 415V
07.5 / 09.0
10.9 / 13.0
11.3 / 13.5
14.4 / 17.2
16.9 / 20.2
22.6 / 26.9
33.8 / 40.4
Voltage
Stages
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
2
2
1
2
2
2
2
—-
—-
—-
—-
—-
—-
12.6 / 15.1
—-
8.7 / 10.4
11.7 / 13.9
—-
7.4 / 8.9
9.9 / 11.8
14.8 / 17.7
—-
—-
Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (C0) across Elect Htr = (kW x 2985)/( m3/h)
Table PD-24A — Air Temperature Rise Across Electric Heaters (Degrees F)
kW
2000 CFM
TSC060AD
11.9 / 14.2
17.2 / 20.5
—-
2400 CFM
TSC072AD
—-
—-
14.9 / 17.8
—-
22.3 / 26.6
29.8 / 35.4
—-
3000 CFM
TSC090AD
—-
—-
11.9 / 14.2
—-
17.8 / 21.3
23.8 / 28.3
—-
3400 CFM
TSC102AD
—-
4000 CFM
TSC120AD
—-
380V / 415V
07.5 / 09.0
10.9 / 13.0
11.3 / 13.5
14.4 / 17.2
16.9 / 20.2
22.6 / 26.9
33.8 / 40.4
Voltage
Stages
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
2
2
1
2
2
2
2
—-
—-
—-
—-
—-
—-
22.8 / 27.2
—-
15.7 / 18.8
21.0 / 25.0
—-
13.4 / 16.0
17.9 / 21.3
26.7 / 31.9
—-
—-
Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (F0) across Elect Htr = (kW x 3414)/(1.08 x CFM)
RT-PRC016-EN
32
Zone Controls
Non-programmable manual auto
changeover with digital LCD Display —
Auto, heat, cool or off mode selection
button. Auto or off fan bottom. Status
indication LCD indicators — System on,
heat, cool, or service.
Zone Sensors
Conventional Thermostats
Zone Sensors are the building
occupant’s comfort control devices for
Precedent™ units with the ReliaTel
control. The zone sensor offering
operates with the Reliatel
Conventional Thermostats are the
building occupant’s comfort control
devises when a generic thermostat is
desired.
Manual
microprocessor
Changeover —
One Heat, One
Cool Thermostat.
Heat, Cool or Off
System Switch.
Fan Auto or On
Switch. Set Point
Dial. Adjustable
Heat Anticipator.
Manual Changeover — Heat, Cool or Off
System Switch. Fan Auto or Off Switch.
One
temperature
setpoint lever.
Automatic Changeover — One Heat,
Two CoolThermostat. Off, Auto System
Switch. Auto/On Fan Switch.
Programmable Night Setback — Auto
or manual changeover with seven-day
programming. Keyboard selection of
Heat, Cool, Fan, Auto, or On.
Manual/Automatic Changeover —Auto,
Heat, Cool or Off System Switch. Fan
Auto or Off
All programmable sensors have
Switch. Two
temperature
setpoint
levers. Optional
Status Indication
LED lights,
Programmable Electronic Night Setback
Thermostat — Heating setback and
cooling setup with 7-day, programming
capability. Available in two-stage
heating/cooling or one-stage heating/
cooling versions with automatic
changeover.
System On,
Heat, Cool, or
Service.
System On, Heat, Cool, Service LED/
indicators as standard. Night Setback
Sensors have one (1) Occupied, one (1)
Unoccuped, and two (2) Override
programs per day.
Integrated Comfort™ System —
Sensor(s) available with optional
temperature
Remote Sensor — Sensor(s) available
for all zone sensors to provide
remote sensing
capabilities.
adjustment and
override buttons
to provide
central control
through a Trane
Integrated
Comfort™
system.
RT-PRC016-EN
33
Electrical
Data
Table ED-1 — Unit Wiring
Standard Indoor Fan Motor
Oversized Indoor Fan Motor
Unit
Minimum
Maximum Fuse
Minimum
Maximum Fuse
Unit
Operating
Voltage Range
342-456
Circuit
Ampacitiy
17.7
23.2
24.8
Size Or Maximum
Circuit
Ampacitiy
17.7
24.2
26.5
Size Or Maximum
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Circuit Breaker1
Circuit Breaker1
25
35
35
35
40
25
35
35
35
40
342-456
342-456
342-456
342-456
26.8
31.2
28.5
31.2
Notes:
1. All units to be installed under local codes
Table ED-2 — Unit Wiring With Electric Heat Single Point Connection — 380-415 Volts
Standard Indoor Fan Motor
Oversized Indoor Fan Motor
Minimum
Circuit
Maximum Fuse
Minimum
Circuit
Maximum Fuse
Size Or Maximum
Circuit Breaker1
25 / 25
Unit
Model No.
TSC060AD
Heater
Model No.
Heater2
MBH
Control
Stages
Size Or Maximum
Circuit Breaker1
25 / 25
kW Rating
7.5 / 9.0
Ampacitiy
19.8 / 21.0
26.1 / 28.0
32.8 / 35.3
26.9 / 28.9
37.5 / 40.5
48.3 / 52.1
28.1 / 30.1
38.8 / 41.8
49.5 / 53.4
38.8 / 41.8
49.5 / 53.4
40.9 / 43.9
51.6 / 55.5
73.1 / 79.0
Ampacitiy
19.8 / 21.0
26.1 / 28.0
32.8 / 35.3
28.1 / 30.1
38.8 / 41.8
49.5 / 53.4
30.3 / 32.3
40.9 / 43.9
51.6 / 55.5
40.9 / 43.9
51.6 / 55.5
40.9 / 43.9
51.6 / 55.5
73.1 / 79.0
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRT427A
BAYHTRT436A
BAYHTRT427A
BAYHTRT436A
BAYHTRT454A
26 / 31
38 / 45
50 / 59
39 / 47
58 / 69
78 / 92
39 / 47
58 / 69
78 / 92
58 / 69
78 / 92
58 / 69
78 / 92
116 / 138
2
2
2
1
2
2
1
2
2
2
2
2
2
2
10.9 / 13.0
14.4 / 17.2
11.3 / 13.5
16.9 / 20.2
22.6 / 26.9
11.3 / 13.5
16.9 / 20.2
22.6 / 26.9
16.9 / 20.2
22.6 / 26.9
16.9 / 20.2
22.6 / 26.9
33.8 / 40.4
30 / 30
35 / 40
35 / 35
40 / 45
50 / 60
35 / 35
40 / 45
50 / 60
40 / 45
50 / 60
45 / 45
60 / 60
30 / 30
35 / 40
35 / 35
40 / 45
50 / 60
35 / 35
45 / 45
60 / 60
45 / 45
60 / 60
45 / 45
60 / 60
TSC072AD
TSC090AD
TSC102AD
TSC120AD
80 / 80
80 / 80
Notes:
1. All units to be installed under local codes
2. kW and MBH shown for 380V / 415V
Table ED-3 — Electrical Characteristics - Evaporator Fan Motor - 50 Hz
Standard Evaporator Fan Motor
Oversized Evaporator Fan Motor
Unit
Amps
Amps
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
No.
1
1
1
1
Volts
Phase
HP
1.5
1.5
2.0
2.0
3.0
FLA
4.3
4.3
5.3
5.3
7.0
LRA
25.3
25.3
36.4
36.4
57.0
No.
Volts
-
380-415
380-415
380-415
-
Phase
-
3
3
3
-
HP
-
2.0
3.0
3.0
-
FLA
-
5.3
7.0
7.0
-
LRA
-
36.4
57.0
57.0
-
380-415
380-415
380-415
380-415
380-415
3
3
3
3
3
-
1
1
1
-
1
Table ED-4 — Electrical Characteristics - Compressor Motor and Condenser Motor - 50 Hz
Compressor Motor
Condenser Fan Motor
Unit
Amps
Amps
1
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
No.
1
1
1
2
Volts
Phase
HP
RPM
2875
2875
2875
2875
2875
RLA1
9.5
12.7
13.20
9.3/6.9
9.9/8.5
LRA1
74.00
95.00
100.00
No.
Phase
HP
FLA
1.9
2.8
2.8
2.8
2.8
LRA
2.8
7.1
7.1
7.1
380-415
380-415
380-415
380-415
380-415
3
3
3
3
3
5.7
7.5
8.3
6.0/3.8
6.0/4.8
1
1
1
1
1
1
1
1
1
1
0.40
0.75
0.75
0.75
0.75
74.0/48.0
74.0/61.8
2
7.1
Note:
1. Comp1/Comp2
RT-PRC016-EN
34
Jobsite
Connections
Zone Sensors — Typical Number Of Wires
DISCONNECT
SWITCH
(BY OTHERS)
A — Manual Changeover . . . . . . . . . . . . . . . . . 4
Manual/Auto Changeover . . . . . . . . . . . . . 5
Manual/Auto Changeover with
ZONE SENSOR
OR THERMOSTAT
Status Indication LED’s . . . . . . . . . . . . . 10
Programmable Night Setback with
Status Indication LED’s . . . . . . . . . . . . . . 7
ROOFTOP
UNIT
Thermostats —Typical Number of Wires
A — 3 wires, 24-volts, Cooling Only
4 wires, 24-volts, with Electric Heat
B — 3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)
For specific wiring information, see the installation instructions.
All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.
RT-PRC016-EN
35
Dimensional
Data
TSC060
All dimensions are in inches/millimeters.
TSC060
RT-PRC016-EN
36
Dimensional
Data
TSC060
All dimensions are in inches/millimeters.
TSC060 — Downflow Airflow Supply/Return
TSC060 — Horizontal Airflow Supply/Return
TSC060 — Unit Clearance and Roof Opening
RT-PRC016-EN
37
Dimensional
Data
TSC060
All dimensions are in inches/millimeters.
TSC060 — Roof Curb
TSC060 — Downflow Duct Connections — Field Fabricated
RT-PRC016-EN
38
Dimensional
Data
TSC072-120
All dimensions are in inches/millimeters.
TSC072-090
TSC102-120
RT-PRC016-EN
39
Dimensional
Data
TSC072-120
All dimensions are in inches/millimeters.
TSC072-120 — Downflow Airflow Supply
and Return
TSC072-120 — Horizontal Airflow Supply
and Return
TSC072-120 — Unit Clearance and Roof
Opening
RT-PRC016-EN
40
Dimensional
Data
TSC072-120
All dimensions are in inches/millimeters.
TSC072-120 — Roof Curb
TSC072-120 — Downflow Duct Connections —
Field Fabricated
ALL FLANGES 1 1/4” (31 MM)
RT-PRC016-EN
41
TSC060
Options/Accessories
Dimensional
Data
All dimensions are in inches/millimeters.
TSC060 — Barometric Relief Damper Hood
TSC060 — Economizer , Manual or Motorized Fresh Air Damper
TSC060 — Swing Diameter for Hinged Doors Option
RT-PRC016-EN
42
TSC072-120
Options/Accessories
Dimensional
Data
All dimensions are in inches/millimeters.
TSC072-120 — Economizer and Barometric
Relief Damper Hoods
TSC072-120 — Swing Diameter for
Hinged Door(s) Option
RT-PRC016-EN
43
Weights
Table W-1 - Maximum Unit and Corner Weights and Center of Gravity Dimensions (SI)
MaximumWeights(2) (kg)
Corner Weights(1) (kg)
Center of Gravity (mm)
Unit
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Shipping(2)
270
Net(2)
235
326
389
405
445
A
75
107
131
133
147
B
56
83
101
106
115
C
D
56
78
89
94
104
Length
790
970
970
990
Width
480
560
530
560
48
58
67
72
81
373
436
453
493
990
560
Notes:
(1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
(2) Weights are approximate.
Table W-1a - Maximum Unit and Corner Weights and Center of Gravity Dimensions (IP)
MaximumWeights (lbs)
Corner Weights(1) (lbs)
Center of Gravity (in)
Unit
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Shipping(2)
595
823
962
998
1087
Net
518
718
857
893
982
A
B
C
D
Length
31
38
38
39
Width
165
235
289
294
323
124
182
222
233
253
105
128
148
159
178
124
173
197
207
229
19
22
21
22
22
39
Notes:
(1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
(2) Weights are approximate.
Table W-2a - Accessory Net Weights(1) (2) (lbs)
Table W-2 - Accessory Net Weights(1) (2) (kg)
Net Weights(2)
Net Weights(2)
TSC072-120
Accessory(3)
Economizer
TSC060
26
TSC072-120
Accessory(3)
TSC060
36
10
30
26
115
8
20
12
30
Economizer
12
3
9
7
32
2
16
5
14
12
52
4
9
5
14
Barometric Relief
Motorized Outside Air Damper
Manual Outside Air Damper
Roof Curb
7
20
16
70
Barometric Relief
Motorized Outside Air Damper
Manual Outside Air Damper
Roof Curb
Oversized Motor
Coil Guards
Oversized Motor
Coil Guards
5
12
5
Hinged Doors
10
Hinged Doors
5
Electric Heaters
15
Electric Heaters
7
Notes:
Notes:
(1) Weights for options not listed are < 5 lbs.
(1) Weights for options not listed are < 3 kg.
2) Net weight should be added to unit weight when ordering factory-installed
accessories.
(3) Some accessories not available on all units.
(2) Net weight should be added to unit weight when ordering factory-installed
accessories.
(3) Some accessories not available on all units.
RT-PRC016-EN
44
Mechanical
Specifications
General
UnitTop
Outdoor Fans
The units shall be convertible airflow.The
operating range shall be between 46°C
and -18°C (115°F and 0°F) in cooling as
standard from the factory for all units. All
units shall be factory assembled,
internally wired, fully charged with R-22,
and 100 percent run tested to check
cooling operation, fan and blower
rotation, and control sequence before
leaving the factory.Wiring internal to the
unit shall be colored and numbered for
simplified identification.
The top cover shall be one piece
construction or where seams exist, it
shall be double-hemmed and gasket-
sealed. The ribbed top adds extra
strength and prevents water from
pooling on unit top.
The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw-through in the vertical discharge
position. The fan motor shall be
permanently lubricated and shall have
built-in thermal overload protection.
Filters
Indoor Fan
One inch, throwaway filters shall be
standard on all 5 ton units.The filter rack
can be converted to two inch capability.
50 mm (2 inch) filters shall be factory
supplied on all 6-10 ton units. Optional 50
mm (2 inch) pleated filters shall be
available.
All units shall have belt drive motors.
Units with belt drive motors shall have
an adjustable idler-arm assembly for
quick-adjustment to fan belts and motor
sheaves. All motors shall be thermally
protected. Oversized motors shall be
available for high static operations.
Casing
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
Compressors
Controls
All units shall have direct-drive, hermetic,
scroll type compressors with centrifugal
type oil pumps. Motor shall be suction
gas-cooled and shall have a voltage
utilization range of plus or minus 10
percent of unit nameplate voltage.
Internal overloads shall be provided with
the scroll compressors. Low and high
pressure switches shall be standard.
Unit shall be completely factory-wired
with necessary controls and contactor
pressure lugs or terminal block for
power wiring. Units shall have single
point power connection as standard.
Unit shall provide an external location
for mounting a fused disconnect device.
weather-resistant baked enamel finish.
Cabinet construction shall allow for all
maintenance on one side of the unit.
Service panels shall have lifting handles
and be removed and reinstalled by
removing only a single fastener while
providing a water and air tight seal. All
exposed vertical panels and top covers in
the indoor air section shall be insulated
with a cleanable foil-faced, fire-retardent
permanent, odorless glass fiber material.
The base of the unit shall be insulated
with 13 mm, 16 kg (1/2 inch, 1 pound)
density foil-faced, closed-cell material. All
insulation edges shall be either captured
or sealed.The unit’s base pan shall have
no penetrations within the perimeter of
the curb other than the raised 29 mm (11/8
inch high downflow supply/return
openings to provide an added water
integrity precaution, if the condensate
drain backs up.The base of the unit shall
have provisions for forklift and crane
lifting, with forklift capabilities on three
sides of the unit.
Microprocessor controls provide for all
24 volt control functions. The resident
control algorithms shall make all
heating, cooling, and/or ventilating
decisions in response to electronic
signals from sensors measuring indoor
and outdoor temperatures. The control
algorithm maintains accurate
temperature control, minimizes drift
from set point, and provides better
building comfort. A centralized
Microprocessor shall provide anti-short
cycle timing and time delay between
compressors to provide a higher level of
machine protection.
Refrigerant Circuits
Service pressure ports, and refrigerant
line filter driers are factory-installed as
standard. An area shall be provided for
replacement suction line driers.
Evaporator and Condenser Coils
Internally finned, 8 mm (5/16”) copper
tubes mechanically bonded to a
configured aluminum plate fin shall be
standard. Coils shall be leak tested at the
factory to ensure the pressure integrity.
The evaporator coil and condenser coil
shall be leak tested to 1375 kPa (200 psig)
and pressure tested to 3100 kPa (450
psig).The condenser coil shall have a
patent pending 1 + 1 + 1 hybrid coil
designed with slight gaps for ease of
cleaning. A removeable, reversible,
double-sloped condensate drain pan with
provision for through the base
condensate drain is standard.
RT-PRC016-EN
45
Mechanical
Specifications
Economizer
Discharge Air Sensing
Accessories/Options
This accessory shall be either field or
factory-installed and shall be available
with or without barometric relief.The
assembly includes fully modulating 0-100
percent motor and dampers, minimum
position setting, preset linkage, wiring
harness with plug, spring return actuator
and fixed dry bulb control.The barometric
relief shall provide a pressure operated
damper that shall be gravity closing and
shall prohibit entrance of outside air
during the equipment “off” cycle.
Optional solid state or differential
enthalpy control shall be available for
either factory or field installation.The
factory-installed economizer arrives in
the shipping position and shall be moved
to the operating position by the installing
contractor.
This factory of field-installed option
provides true discharge air sensing in
heating models.This sensor is a status
indicator readable throughTracer™ or
Tracker™.
Electric Heaters
Field-installed electric heat modules shall
be available for installation within basic
unit. Electric heater elements shall be
constructed of heavy-duty nickel
chromium elements internally delta
connected for 200 volt, wye connected
for 380-415 volt. Staging shall be
achieved through the unitary control
processor (UCP). Each heater package
shall have automatically reset high limit
control operating through heating
element contactors. All heaters shall be
individually fused from the factory, where
required. Power assemblies shall provide
single-point connection.
Oversized Motors
Factory or field-installed oversized
motors shall be available for high static
applications.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is
available, factory-installed, to achieve
active fan failure indication and/or
clogged filter indication.These indications
will be registered with either a zone
sensor with status indication lights or an
Integrated Comfort™ System.
Roof Curb
High Pressure Cutout
Standard on all units.
The roof curb shall be designed to mate
with the unit’s downflow supply and
return and provide support and a water
tight installation when installed properly.
The roof curb design shall allow field-
fabricated rectangular supply/return
ductwork to be connected directly to the
curb. Curb shall be shipped knocked down
for field assembly and shall include wood
nailer strips.
Phase Monitor
Phase monitor shall provide 100%
protection for motors and compressors
against problems caused by phase loss,
phase imbalance, and phase reversal.
Phase monitor is equipped with an LED
that provides an ON or FAULT indicator.
Hinged Access Doors
Sheet metal hinges are available factory-
installed on the Filter/Evaporator, Supply
Fan/Heat, and the Compressor/Control
Access Doors.
Black Epoxy Coated Condenser Coil
The coil provides corrosion protection to
condenser coils for seacoast application.
The protection is a factory-applied
thermoset vinyl coating, bonded to
normal aluminum fin stock.The uniform
thickness of the bonded vinyl layer
exhibits excellent corrosion protection.
Remote Potentiometer
The minimum position setting of the
economizer shall be adjusted with this
accessory.
Manual Outside Air Damper
Factory or field-installed rain hood and
screen shall provide up to 50 percent
outside air.
Motorized Outside Air Dampers
Factory or field-installed manually set
outdoor air dampers shall provide up to
50 percent outside air. Once set, outdoor
air dampers shall open to set position
when indoor fan starts.The damper shall
close to the full closed position when
indoor fan shuts down.
RT-PRC016-EN
46
Mechanical
Specifications
Differential Pressure Switches
Control Options
Comm-3/4Trane Communication
Interface
This factory or field-installed option shall
be provided to interface microprocessor
controlled units with theTrane Integrated
Comfort™ systems.
These factory or field-installed sensors
allow individual fan failure and dirty filter
indication for microprocessor controlled
units.The fan failure switch will disable all
unit functions and “flash” the Service
LED on the zone sensor.The dirty filter
switch will light the Service LED on the
zone sensor and will allow continued unit
operation.
Comm-5 LonTalk Communication
Interface
This factory or field-installed option shall
be provided to allow the unit to
communicate as aTrane Comm-5 device
or directly with generic LonTalk Network
Building Automation System Controls.
Reference Enthalpy Control
Replaces the dry bulb control with a wet
bulb changeover controller which has a
fully adjustable set point. Enthalpy control
offers a higher level of comfort control,
along with energy savings potential, than
the standard dry bulb control.This is due
to the additional wet bulb sensing
Zone Sensor
This field-installed control shall be
provided to interface with the Micro
equipped units and shall be available in
either manual, automatic programmable
with night setback, with system
malfunction lights, or remote sensor
options.
capability.This option shall be available
for microprocessor controlled units. It can
be field-installed, or factory-installed with
the factory-installed economizer.
Differential Enthalpy Control
Thermostats
Replaces the standard dry bulb control
with two enthalpy sensors that compare
total heat content of the indoor air and
outdoor air to determine the most
efficient air source.This control option
offers the highest level of comfort control,
plus energy efficiency, available.This
option shall be available for
Two stage heating and cooling operation
or one stage heating and cooling shall be
available, for field installation, in either
manual or automatic changeover.
Automatic programmable electronic with
night set back shall also be available.
microprocessor controlled units. It can be
field-installed, or factory-installed with the
factory-installed economizer.
LowAmbient Cooling
All microprocessor units shall have
cooling capabilities down to 18°C (0°F) as
standard.
RT-PRC016-EN
47
Literature Order Number
File Number
RT-PRC016-EN
PL-UN-000-RT-PRC016-EN-02-04
PL-UN-000-RT-PRC016-EN-12-03
03-03Webb/Mason 02-04 Electronic Only
Supersedes
Trane
A business of American Standard Companies
Stocking Location
Trane has a policy of continuous product and product data improvement and reserves the right to change
design and specifications without notice
For more information, contact your local district
office or e-mail us at comfort@trane.com
|
Teac Stereo System MC DX80I User Manual
Toyota Automobile MCV10 User Manual
Transcend Information MP3 Player T sonic 310 User Manual
Triarch Indoor Furnishings 31082 32 User Manual
Tripp Lite Power Supply SUPDM16 User Manual
Tyco Network Card Escort5580TC User Manual
Uniden Cordless Telephone WDSS 5335 WDSS 5335 User Manual
Vista Home Security System N7227V5 User Manual
Vulcan Hart Fryer 1ER50A User Manual
Weber Charcoal Grill 120409 User Manual